Heat Pump
50Hz/R410A _ 1
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
1.1 Power supply
External wiring procedure
- The power supply work is needed only to the outdoor unit. The power supply to the indoor unit is conducted through the
transmission wiring. Therefore, the power supply work can be carried out at just one place of the outdoor unit. It will
contribute to simplify the work procedure and to save cost.
- Wiring cable size must comply with the applicable local and national code.
Outdoor unit
[Indoor unit]
Power supply
Circuit breaker
Earth wire
Type Outdoor unit Capacity[kBtu/h(kW)]
Circuit breaker capacity
Power supply
Heat Pump
A2UW14GFA0 [MU2M15 UL2] 14.0 (4.10)
15A
220-240V, 1Ø, 50Hz
A2UW16GFA0 [MU2M17 UL2] 16.0 (4.69)
A3UW18GFA0 [MU3M19 UE2] 18.0 (5.27)
20A
A3UW21GFA0 [MU3U21 UE2] 21.0 (6.15)
A4UW24GFA0 [MU4M25 U42] 24.0 (7.03)
25AA4UW27GFA0 [MU4M27 U42] 27.0 (7.91)
A5UW30GFA0 [MU5M30 U42] 30.0 (8.79)
A5UW40GFA0 [MU5M40 UO2] 38.2 (11.2) 30A