8 Indoor Unit
Installation
Installation
Indoor unit
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit’s weight.
• Sufficient space should be available to inspect the unit as in
the figure shown on the right.
• The place where the unit is installed shall be leveled.
• The place shall be suitable for easy connection of the indoor
unit with the outdoor unit.
• The place where the unit is installed should not be affected
by electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit
Service space
Select an installation site where the following conditions are
satisfied and that meets your customer's approval.
• Where the floor is strong enough to bear the indoor unit
weight.
• Where the floor is not significantly inclined.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where sufficient clearance for installation and maintenance
can be ensured.
• Where there is no possibility of flammable gas leakage.
• Where optimum air distribution can be ensured.
• Where piping between indoor and outdoor units is possible
within the allowable limit (Refer to the installation manual of
the outdoor unit.)
• Keep the indoor and outdoor unit, power cable and trans-
mission wiring, at least 1m from TVs and radios, to prevent
distorted pictures and static.(Depending on the type and
source of the electrical waves, static may be heard even
when more than 1 m away.)
Selection of the best location
654(25-3/4)
80(2-3/16) or more
B or more
Maintenance area
Window
A or more
20(3/4) or
more
100(5-7/8)
or
more
100(3-15/16)
or
more
175(6-7/8)
or
more
150(5-7/8)
or
more
Front side
Base
Unit:mm(inch)
Air flow
direction
Air inlet
direction
1000(39-3/8)
or
more
Window
[IMPORTANT]
Leave sufficient clearance
for air inlet and maintenance.
Type A B
CEU Type 788(31) 1080(42-
1
/2)
CFU Type 1066(42) 1358(53-
1
/2)
[Unit: mm(inch)]