TEST RUN
ENGLISH
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1” ~ “op4” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Target pressure is set
Select the Option using ‘’, ‘’ Button :
“HEAT” , “COOL” Push the ‘’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
“Heat” “Cool”
op1 Increase capacity Increase capacity
-3°C(26.6°F) +2°C(35.6°F)
op2
Decrease power consumption
Increase capacity
-1.5°C(29.3°F) -2°C(28.4°F)
op3
Decrease power consumption Decrease power consumption +2.5°C(36.5°F) -4°C(24.8°F)
op4
Decrease power consumption Decrease power consumption -4.5°C(23.9°F) -6°C(21.2°F)
Target pressure adjusting
mode setting method

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V ARUN***CTE4 and is the answer not in the manual?

LG MULTI V ARUN***CTE4 Specifications

General IconGeneral
BrandLG
ModelMULTI V ARUN***CTE4
CategoryAir Conditioner
LanguageEnglish

Related product manuals