14
|
PRODUCT DATA
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Table 1a: General Data—Outdoor Units
3.0 Ton
ARUN036GS2
4.0 Ton
ARUN047GS2
4.4 Ton
ARUN053GS2
Cooling Mode Performance
Cooling Capacity (Btu/h) 38,000 48,000 53,000
Power Input (kW) 3.1 4.25 5.51
EER (System) / EER (ODU)
3
11.10 / 12.26 9.50 / 11.29 9.00 / 9.62
System SEER
3
15.90 15.20 14.50
Heating Mode Performance
Heating Capacity (Btu/h) at 47°F 42,000 53,500 59,000
Heating Capacity (Btu/h) at 17°F 26,400 32,000 38,000
Power Input (kW) 3.4 4.3 5.6
COP (ODU)
3
3.62 3.65 3.90
System HSPF
3
8.50 9.20 8.50
Operating Range
Cooling (°F DB) 23–118 23–118 23–118
Heating (°F) (-4)–60 (-4)–60 (-4)–60
Compressor
Inverter Rotary Quantity 1 1 1
Oil / Type PVE / FVC68D PVE / FVC68D PVE / FVC68D
Full Load Operating RPM 3600 3600 3600
Unit Data
Refrigerant Type R410A R410A R410A
Refrigerant Control / Location EEV / Indoor Unit EEV / Indoor Unit EEV / Indoor Unit
Maximum Number Outdoor Units / System
1
111
Maximum Number Indoor Units / System
1
689
Minimum Number Indoor Units / System
1
111
Qty Refrigeration Circuits 1 1 1
Sound Pressure Cooling / Heating dB(A)
5
50 / 52 51 / 53 52 / 54
Net Unit Weight (lbs) 234 234 234
Shipping Weight (lbs) 258 258 258
Communication Cable (Qty # Wires / Gauge)
2
2 / 18 2 / 18 2 / 18
Fan
Type Propeller (BLDC) Propeller (BLDC) Propeller (BLDC)
Qty / Motor HP 2 / 0.166 2 / 0.166 2 / 0.166
Qty / Diameter (in) 2 / 20.75 2 / 20.75 2 / 20.75
Motor / Drive Brushless Digitally-Controlled / Direct Brushless Digitally-Controlled / Direct Brushless Digitally-Controlled / Direct
Operating Range (RPM) 80–950 80–950 80–950
Maximum Air Volume (CFM) 3,885 3,885 3,885
Maximum External Static Pressure (in-wg) 0.16 0.16 0.16
Air ow Direction Horizontal—Back to Front Horizontal—Back to Front Horizontal—Back to Front
Outdoor Units
1. The System Combination Ratio must be
between 50–130%. See page 55 for more
information.
2. All communication cables must comply with
applicable local codes.
3. Rated using non-ducted indoor units. Rated
0 ft. above sea level with 25 ft. of refrigerant
line per indoor unit and a 0 ft. level difference
between outdoor and indoor units. All capaci-
ties are net with a Combination Ratio between
95–105%. Certi ed under the AHRI Unitary
Small Heat Pump equipment certi cation pro-
gram and tested per AHRI Standard 210/240
conditions and in accordance with DOE test
procedures. Nominal Cooling capacity rating
obtained with air entering the indoor coil at
80°F dry bulb (DB) and 67°F wet bulb (WB)
and outdoor ambient conditions of 95°F dry
bulb (DB) and 75°F wet bulb (WB). Nominal
Heating capacity rating obtained with air
entering the indoor unit at 70°F dry bulb (DB)
and 59°F wet bulb (WB) and outdoor ambient
conditions of 47°F dry bulb (DB) and 43°F
wet bulb (WB).
4. Unit is capable of operating outside the
operating range temperature limitations. See
"Select the Outdoor Unit" on page 52.
5. Sound pressure levels are tested in an
anechoic chamber under ISO Standard 1996.
6. Power wiring cable is eld provided and must
comply with the applicable local and national
codes.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V mini and is the answer not in the manual?

LG Multi V mini Specifications

General IconGeneral
BrandLG
ModelMulti V mini
CategoryHeat Pump
LanguageEnglish

Related product manuals