51
Wiring
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
If power wires are not properly terminated
and firmly attached, there is risk of fire,
electric shock, and physical injury or death.
Never ground the shield of the com-
munications cable to the indoor unit frame
or other grounded entities of the building.
Failure to properly provide a National Elec-
trical Code-approved earth ground can
result in electric shock, physical injury or
death.
Never apply line voltage power to the communications cable terminal block. If contact is made, the PCBs may be damaged.
Always include some allowance in the wiring length when terminating. Provide some slack to facilitate removing the electrical panels while
servicing.
:Copper Wire
Terminate multiple power wires of
the same gauge to both sides.
Do not terminate two wires on
one side.
Do not terminate different gauge
wires to a terminal block.
Figure 60: Proper and Improper Power Wiring Connections
Communication Cable Specifications
Between Outdoor Unit and Indoor Units
• Use a two-core, stranded, shielded or unshielded cable minimum 18 gauge between the Multi V S outdoor unit and the indoor units. If shielded,
cable must be grounded to the chassis at the outdoor unit only.
Insulation material as required by local code.
5DWHGIRUFRQWLQXRXVH[SRVXUHRIWHPSHUDWXUHVXSWR)
0D[LPXPDOORZDEOHFDEOHOHQJWKIHHW
Ring and spade terminals used to connect communications cables MUST be copper bearing.
Do NOT use terminals that are galvanized
or nickel plate over steel.
)LUPO\DWWDFKWKHFDEOHSURYLGHVODFNEXWVHFXUHLQDZD\WRSUHYHQWH[WHUQDOIRUFHVIURPEHLQJLPSDUWHGRQWKHWHUPLQDOEORFN
Communications cable connecting the Multi V S outdoor unit and indoor unit(s) should be installed and terminated in a daisy chain (BUS)
configuration starting at the Multi V S outdoor unit.
Wiring should be completed without splices.
Always verify the communication cable is connected to a communications terminal on the Multi V S unit. Never apply line voltage power to the
communication cable connection. If contact is made, the PCBs may be damaged.
Position the Multi V S outdoor unit communications cables away from the power wiring. Refer to minimum spacing requirements provided in
Table 30.
Never use a common multiple-core communications cable. Each communications bus shall be provided a separate cable (i.e., between
Multi V S outdoor unit and indoor units, Multi V S outdoor units and central controller(s). If communications cables of separate systems are
wired using a common multiple-core cable, it will result in a poor communications signal and unacceptable system operation.
Figure 61: 0XOWL966\VWHP&RPPXQLFDWLRQV/DEHOLQJ6FKHPDWLF
5HFRPPHQGHG²7ZR&RUH6WUDQGHG6KLHOGHGRU8QVKLHOGHG
&DEOHLQD'DLV\&KDLQ&RQ¿JXUDWLRQ
,PSURSHUO\7HUPLQDWHG&RPPXQLFDWLRQV&DEOH²0XOWLSOH&RUH
&DEOHLQD6WDUEXUVW&RQ¿JXUDWLRQ
WIRING
&RPPXQLFDWLRQV&DEOH6SHFL¿FDWLRQV

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V S ARUN038GSS4 and is the answer not in the manual?

LG MULTI V S ARUN038GSS4 Specifications

General IconGeneral
BrandLG
ModelMULTI V S ARUN038GSS4
CategoryAir Conditioner
LanguageEnglish

Related product manuals