User menus and parameters
46 Air-to-Water Heat Pump
Normal 19.9 10.0…19.9
The desired temperature of cooling in the Normal mode of
operation.
Eco -2.0 0.0…10.0
Lowering the desired temperature in the Eco mode of
operation.
Comfort 2.0 -10.0…0.0
Raising the desired temperature in the Comfort mode of
operation.
Hysteresis 3.0 0.0…10.0
By setting this parameter we change the desired tempera-
ture of the restarted device with the parameter Standby
from 0 °C to 10 °C.
Example:
The parameter Cooling is set to 23 °C.
The device will be in standby from 20 °C to 23 °C.
The parameters are adjusted only in case of active cooling.
T.outside min 20 0.0…55.0
Setting the external temperature above which the cooling
will activate.
Max 40 0.0…55.0
Setting the external temperature at which the cooling will
deactivate.
1. CIRCUIT/
2. CIRCUIT/
3. CIRCUIT/
4. CIRCUIT
Parameter
name
Adjustable
value
Scope [°C] Parameter description
C/W I
By setting this parameter we lower the temperature for up
to 4 °C or raise it for up to 4 °C.
Example: I>> means that the currently set temperature of
the circuit (the setting in the parameter Normal) is raised
for 2°C.
Schedule For settings see chapter (Schedules)
Normal 19.9 19.9…max.
By setting this parameter we change the desired tempera-
ture in the Normal operating mode of the HP.
Eco -2.0 -10.0…0.0
By setting this parameter we change the desired tempera-
ture in the ECO operating mode of the HP.
Comfort 2.0 0.0…10.0
By setting this parameter we change the desired tempera-
ture in the Comfort operating mode of the HP.
Hysteresis 2.0 0.0…10.0
By setting this parameter we change the desired tempera-
ture of the Hysteresis parameter of the mixing valve from
0 °C to 10 °C.
Example:
The parameter Hysteresis is 50 °C.
The mixing valve will be in standby from 48 °C to 52 °C.
Const.
temperatur
50
Heating with constant temperature Const.
Temperature or optimised heating according to external
temperature Heating Curve.