Line Voltage Wiring Details
Use properly certified cable for all line
voltage/mains cables.
Proper short-circuit and overload
protection must be provided at the
distribution panel.
Install in accordance with all local and
national electrical codes.
IEC PELV/NEC® Class 2 terminals may
be temporarily unplugged for ease of
contact closure and control wiring.
Notice: Risk of damage to unit. Do not
connect line voltage/mains cable to IEC
PELV/NEC® Class 2 terminals.
Step 1: Install wallbox. Mount a 3` in
(89 mm) deep 4-gang U.S. wallbox on a
dry, flat indoor surface that is accessible
and allows for system programming and
operation. Allow at least 4` in (110 mm)
clearance above and below the faceplate
to ensure proper heat dissipation. Allow
1 in (25 mm) for faceplate overhang on
all sides.
Note: 4-gang wallbox available from
Lutron; P/N 241400.
Step 2: Check wiring.
Earth/ground terminal connection must
be made as shown in wiring diagrams
(see page 3).
Follow all local and national electrical
codes when installing IEC PELV/NEC®
Class 2 wiring with line voltage/mains
wiring.
WARNING! Electric Shock hazard.
May result in Serious Injury or
Death. Always turn off circuit
breaker or remove main fuse from
power line before doing any work.
Step 3: Connect line voltage.
• Strip 9 in (8 mm) of
insulation off the line
voltage/mains cables in
the wallbox.
Connect the line voltage/mains and
ground wires to the appropriate terminals
on the back of the timeclock.
L: Line / Hot
N: Neutral
: Ground
The recommended installation torque is
5.0 inlb (0.6 Nm) for line voltage/mains
connections and 5.0 inlb (0.6 Nm) for
the earth/ground connection.
Notice: Risk of damage to unit.
The QS Timeclock must be in stalled by
a qual i fied electrician in accordance with
all applica ble reg u la tions and building
codes. Im prop er wiring can result
in dam age to the timeclock or oth er
equipment.
QS Timeclock Quick Installation and Operation Guide 4
®
Faceplate overhangs
wallbox on all sides;
allow 1 in (25 mm)
4` in
(110 mm)
9 in
(8 mm)

Table of Contents

Other manuals for Lutron Electronics QS Timeclock

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lutron Electronics QS Timeclock and is the answer not in the manual?

Lutron Electronics QS Timeclock Specifications

General IconGeneral
BrandLutron Electronics
ModelQS Timeclock
CategoryControl Unit
LanguageEnglish

Related product manuals