Section 2 Installation Instructions
Part Number 000007644 3/11 12
C. SUCTION LINE OIL TRAPS
0 to 20 feet (0 to 6.1 m) Rise: No oil trap is required
when the condensing unit is located 20 feet (6.1 m) or
less above the ice machine head section.
21 to 35 feet (6.4 to 10.7 m) Rise: The suction line
requires an additional Oil Trap (“S” type) to be installed.
Install the trap as close as possible to midpoint between
the ice machine head section and remote condensing
unit. S-Trap Kits are available from Manitowoc.
Service Loop
A service loop in the line set permits easy access to the
ice machine for cleaning and service.
A service loop is not considered an oil trap.
The service loop is not included when calculating
length, rise or drop of the tubing run.
Do not use hard rigid copper for the service loop.
Step 3 Lengthening or Reducing Line Set Lengths
When the line set requires shortening or lengthening, do
so before connecting the line set to the ice machine
head section or the remote condensing unit.
!
Caution
Do not form unwanted traps in refrigeration lines.
Never coil excess refrigeration tubing.
21 ft. (6.4 m)
OR MORE RISE
ADDITIONAL
TRAP KIT
REQUIRED
SV1751
SV1760
!
Caution
If a line set has a rise followed by a drop, another rise
cannot be made. Likewise, if a line set has a drop
followed by a rise, another drop cannot be made.
!
Caution
Do not form unwanted traps in refrigeration lines.
Never coil excess refrigeration tubing.