Part Number 000007661 6/13 81
RF0644/RF0650/RF1200/RFS1200
Troubleshooting
SELF-CONTAINED AIR-COOLED
Normal Operation
When the toggle switch is placed in the ON position
the following controls must be in the closed position
before the ice machine will start:
A. Bin Thermostat
B. High Pressure Cut-out Switch
C. Ice Chute Safety Switch
D. Low Pressure Switch
E. Low Water Level Switch
NOTE: Placing the toggle switch in the ON position
starts the gear motor. After the rotation speed sensor
verifies 10
minutes of correct rotation the time delay
ends and the compressor starts.The ice machine will
continue to make ice until ice contacts the bin
thermostat. The ice machine remains off until ice no
longer contacts the bin thermostat.
ROTATION SENSOR OPERATION
light Definition
Yellow Blinking Time Delay Period
Yellow Solid Normal Operation Sensing
Red Blinking Fault Time Delay Period
Red Solid
Lockout - 8 Consecutive Faults
Remove/Restore Power To Reset