Freeze Cycle:
Ice machines that are operating normally will have
consistent maximum discharge line temperatures above
150Β°F (66Β°C).
Verify the expansion valve sensing bulb is positioned and
secured correctly.
ξξξξξξξξξξξΎξξΆξξξ€ξξ΅ξξξξξξ΅ξξξξξξ―ξ½ξξξ§ξ§±ξ§¬ξ¦£ξ¦ξξ₯Ύξ§²ξ§²ξ¦£ξξ₯ΏξξξξξξΆξξξ½ξ¨ξ
Freeze Cycle
Ice machines that have a flooding expansion valve will have
a maximum discharge line temperature that decreases
each cycle.
Verify the expansion valve sensing bulb is 100% insulated
and sealed airtight. Condenser air contacting an incorrectly
insulated sensing bulb will cause overfeeding of the
expansion valve.