100 AGR 055A through 100A IOMM AGR
due to a clogged filter-drier or a restriction elsewhere in the liquid line See Table 55 for maximum
allowable pressure drops. If subcooling is low add charge to clear the sightglass. If subcooling is
normal (10°-15°F) and flashing is visible in the sightglass check the pressure drop across the filter-
drier. Subcooling should be checked at full load with 70°F (21.1°C) outdoor air temperature and all
fans running.
An element inside the sightglass indicates the moisture condition corresponding to a given element
color. If the sightglass does not indicate a dry condition after about 12 hours of operation, the
circuit should be pumped down and the filter-drier changed.
Preventative Maintenance Schedule
PREVENTATIVE MAINTENANCE SCHEDULE
OPERATION WEEKLY MONTHLY
(Note 1)
ANNUAL
(Note 2)
General
Complete unit log and review (Note 3) X
Visually inspect unit for loose or damaged components X
Inspect thermal insulation for integrity X
Clean and paint as required X
Electrical
Check terminals for tightness, tighten as necessary X
Clean control panel interior X
Visually inspect components for signs of overheating X
Verify compressor heater operation X
Megger compressor motor every five years (Note 6)
Test and calibrate all safety and operating controls X
Refrigeration
Leak test X
Check sight glasses for clear flow X
Check filter-drier pressure drop (see manual for spec) X
Condenser (air-cooled)
Clean condenser coils (Note 4) X
Check fan blades for tightness on shaft (Note 5) X
Check fans for loose rivets and cracks X
Check coil fins for damage X
Notes:
1. Monthly operations include all weekly operations.
2. Annual (or spring start-up) operations includes all weekly and monthly operations.
3. Log readings may be taken daily for a higher level of unit observation.
4. Coil cleaning may be required more frequently in areas with a high level of airborne particles.
5. Be sure fan motors are electrically locked out.
6. Caution: Do not Megger motor while in a vacuum.