1-12
5SLY40/50FR
More than 100 More than 500
More
than 100
More
than
100
More than 100
More than 100
More than 500
Allow more space for installation above with additional obstacle at top side and installation in series.
Top View
Side View
Unit: mm
REFRIGERANT PIPING
Indoor 5CKY20E/ER 5CKY25E/ER 5CKY28ER
Outdoor 5SLY20C/CR 5SLY25C/CR 5SLY28CR
Max. allowable length, m 30 30 50
Max. allowable elevation, m 10 10 30
Liquid pipe size, mm/(in) 6.35 (1/4") 6.35 (1/4") 9.52 (3/8")
Gas pipe size, mm/(in) 12.70 (1/2") 15.88 (5/8") 15.88 (5/8")
Additional charge of refrigerant, g/m
(for piping length above 7.5m)
20 20 50
Indoor 5CKY40ER 5CKY50ER
Outdoor 5SLY40FR 5SLY50FR
Max. allowable length, m 75 75
Max. allowable elevation, m 30 30
Liquid pipe size, mm/(in) 9.52 (3/8") 9.52 (3/8")
Gas pipe size, mm/(in) 15.88 (5/8") 15.88 (5/8")
Additional charge of refrigerant, g/m
(for piping length above 30m)
50 50
Allowable Piping Length
When the pipe length becomes too long, both the capacity and reliability drop. As a result, compressor reliability will be
affected. Always choose the shortest path and follow the recommendation as tabulated below:
Wall facing one side
Wall facing more than 1 side of obstacle
1 EN 5CKYER-1009(1).indd 121 EN 5CKYER-1009(1).indd 12 4/21/11 9:11:20 AM4/21/11 9:11:20 AM