1-15
English
3
2
1
3
2
1
L1
L2
L3
N
Power Supply Cable
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
5CKY40ER - 5SLY40FR (1 Phase)
5CKY50ER - 5SLY50FR (1 Phase)
3
2
1
2
1
3
L
N
Interconnection
Cable
Model Indoor 5CKY40ER 5CKY50ER
Outdoor 5SLY40FR 5SLY50FR
Voltage range** Indoor
220V - 240V/1Ph/50Hz + !
Outdoor
220V - 240V/1Ph/50Hz + !
Power supply cable size* mm
2
Number of conductors
6
3
6
3
Interconnection cable size* mm
2
Number of conductors
1.5
4
1.5
4
Recommended time delay fuse* A 32 32
5CKY40ER - 5SLY40FR (3 Phase)
5CKY50ER - 5SLY50FR (3 Phase)
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
!
Model Indoor 5CKY40ER 5CKY50ER
Outdoor 5SLY40FR 5SLY50FR
Voltage range** Indoor
220V - 240V/1Ph/50Hz + !
Outdoor
380V - 415V/3N~/50Hz + !
Power supply cable size* mm
2
Number of conductors
4
5
4
5
Interconnection cable size* mm
2
Number of conductors
1.5
4
1.5
4
Recommended time delay fuse* A 20 20
Power Supply Cable
Indoor Unit
Terminal Block
Interconnection
Cable
Outdoor Unit
Terminal Block
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
!