CEILING CONCEALED HEAT PUMP MODELS (R407C)
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO
26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB
Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER
MODEL
INDOOR UNIT
MCC 030CR
MCC 040CR
MCC 050CR
OUTDOOR UNIT
M4LC 030CR
M4LC 040CR
M4LC 050CR
NOMINAL
kcal/h
7,310
9,830
12,100
COOLING
W
8,499
11,430
14,068
CAPACITY
Btu/h
29,000
39,000
48,000
NOMINAL
kcal/h
7,812
10,332
12,600
HEATING W
9,083
12,013
14,654
CAPACITY Btu/h
31,000
41,000
50,000
POWER SOURCE
V/Ph/Hz
REFRIGERANT / CONTROL
R407C / TXV (OUTDOOR)
AIR FLOW
cfm/cmm
900 / 25.49
1,200 / 33.99
1,500 / 42.49
STATIC PRESSURE
mm Aq
FAN MOTOR
RATED INPUT POWER
W
421
550
670
RATED RUNNING CURRENT
A
1.9
2.6
2.9
MATERIAL
DIAMETER
mm/in
THICKNESS mm/in
MATERIAL
THICKNESS
mm/in
ROW
3
3
3
FIN PER INCH
12
14
14
FACE AREA
m
2
/ft
2
0.27 / 2.98 0.31 / 3.44 0.40 / 4.40
HEIGHT
mm/in
DIMENSION
WIDTH
mm/in
929 / 36.57
1045 / 41.14
1299 / 51.14
DEPTH mm/in
WEIGHT
kg
39
42
54
SOUND PRESSURE LEVEL
dBA
61 / 59 / 57
61 / 59 / 58
62 / 61 / 60
CONTROL
ROOM TEMPERATURE
OPERATION
CONDENSATE DRAIN SIZE mm/in
AIR FILTER
PACKING
HEIGHT
mm/in
DIMENSION
WIDTH
mm/in
1110 / 43.70
1229 / 48.39
1481 / 58.31
DEPTH
mm/in
POWER SOURCE
V/Ph/Hz
220 - 240 / 1 / 50
COMPRESSOR TYPE
CAPACITOR
µF
50
-
-
LOCK ROTOR AMP.
A
78
45
62
RATED RUNNING CURRENT (COOLING)
A
11.5
6.2
8.8
RATED RUNNING CURRENT (HEATING)
A
11.4
5.9
7.8
RATED INPUT POWER (COOLING) W
2,424
3,565
4,615
RATED INPUT POWER (HEATING) W
2,407
3,280
3,734
PROTECTION DEVICE
POWER SOURCE
V/Ph/Hz
FAN TYPE / DRIVE
BLADE MATERIAL
DIAMETER mm/in
RATED RUNNING CURRENT
A
RATED OUTPUT POWER
W
RATED INPUT POWER
W
MATERIAL
DIAMETER mm/in
THICKNESS
mm/in
MATERIAL
THICKNESS
mm/in
ROW
1
2
2
FIN PER INCH
16
14
16
FACE AREA
m
2
/ft
2
HEIGHT
mm/in
DIMENSION
WIDTH
mm/in
DEPTH mm/in
WEIGHT kg
95
100
105
MATERIAL
CASING
THICKNESS
mm/in
FINISHING
SOUND PRESSURE LEVEL
dBA
60
59
62
TYPE
SIZE LIQUID mm/in
9.52 / 3/8
9.52 / 3/8
9.52 / 3/8
GAS
mm/in
15.88 / 5/8
19.05 / 3/4
19.05 / 3/4
PACKING
HEIGHT
mm/in
DIMENSION
WIDTH
mm/in
DEPTH
mm/in
INDOOR UNIT
PIPE
OUTDOOR UNIT
220 - 240 / 1 / 50
378 / 14.88
474 / 18.66
399 / 15.71
615 / 24.21
FIN
OVERLOAD PROTECTION / HI PRESSURE SWITCH
TUBE
FAN
COIL
SEAMLESS BARE COPPER
9.52 / 3/8
0.35 / 0.014
ALUMINIUM
COIL
TUBE
FIN
COMPRESSOR
FAN
ALUMINIUM (CORRUGATED)
0.127 / 0.005
145
241
S.B.C.
220 - 240 / 1 / 50
15 / 10 / 5
4 POLES
0.127 / 0.005
R407C / CAPILLARY TUBE + TXV (OUTDOOR)
MICROCOMPUTER CONTROLLED THERMOSTAT
SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
19.05 / 3/4
FLARE VALVE
WASHABLE SARAN NET
380 - 415 / 3 / 50
PROPELLER / DIRECT
SCROLL
850 / 33.46
1,030 / 40.55
0.87 / 9.33
1,200 / 47.24
560 / 22.05
ELECTRO-GALVANISED MILD STEEL
0.8 / 0.031
POLYESTER POWDER
1,000 / 39.37
400 / 15.75
GLASS REINFORCED ACRYL STYRENE RESIN
610 / 24
9.52 / 3/8
0.35 / 0.014
1.09