10
CEILING CONCEALED HEAT PUMP MODELS (R407C)
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO
26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB
Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER
OUTDOOR UNIT
HEATING W
CAPACITY Btu/h
FAN MOTOR
THICKNESS mm/in
MATERIAL
FACE AREA
2
2
0.27 / 2.98 0.31 / 3.44 0.40 / 4.40
DEPTH mm/in
CONDENSATE DRAIN SIZE mm/in
AIR FILTER
COMPRESSOR TYPE
RATED RUNNING CURRENT (COOLING)
RATED RUNNING CURRENT (HEATING)
RATED INPUT POWER (COOLING) W
RATED INPUT POWER (HEATING) W
DIAMETER mm/in
DIAMETER mm/in
FACE AREA
DEPTH mm/in
WEIGHT kg
SIZE LIQUID mm/in
378 / 14.88
474 / 18.66
615 / 24.21
OVERLOAD PROTECTION / HI PRESSURE SWITCH
SEAMLESS BARE COPPER
9.52 / 3/8
0.35 / 0.014
241
S.B.C.
15 / 10 / 5
4 POLES
R407C / CAPILLARY TUBE + TXV (OUTDOOR)
MICROCOMPUTER CONTROLLED THERMOSTAT
SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
19.05 / 3/4
FLARE VALVE
WASHABLE SARAN NET
380 - 415 / 3 / 50
PROPELLER / DIRECT
SCROLL
0.87 / 9.33
1,200 / 47.24
560 / 22.05
ELECTRO-GALVANISED MILD STEEL
POLYESTER POWDER
400 / 15.75
GLASS REINFORCED ACRYL STYRENE RESIN
610 / 24
9.52 / 3/8