Caution
1. The temperature of the surface of PTC heater may be over 200°C if the power of unit is on but the fan of
the unit is not running. Don’t touch the unit at this time!
2. The starting current of the unit is more than its working current. It should be considered both the working
current and starting current while choosing the fuse.
3. When the MCW200CD~MCW1200CD fan coil unit with PTC heater is running, ENSURE there is no
obstructions to air flow into or out of the unit.
Figure 1
Electric Heating Power (kW)
Unit Size Power Supply
kW kW kW kW kW kW kW kW kW kW kW kW
220V-240V~/50Hz 0.5 1.0 1.5 2.0 - - - - - - - -
MCW200CD
115V~/60Hz 0.5 1.0 1.5 2.0 - - - - - - - -
220V-240V~/50Hz - 1.0 1.5 2.0 2.5 3.0 - - - - - -
MCW300CD
115V~/60Hz - 1.0 1.5 2.0 2.5 3.0 3.5 4.0 - - - -
220V-240V~/50Hz - - - 2.0 2.5 3.0 3.5 - - - - -
MCW400CD
115V~/60Hz - - - 2.0 2.5 3.0 3.5 4.0 - - - -
380V/3N~/50Hz - - - - 2.5 3.0 3.5 4.0 5.0 - - -
MCW600CD
115V~/60Hz - - - - 2.5 3.0 3.5 4.0 5.0 6.0 - -
380V/3N~/50Hz - - - - - 3.0 3.5 4.0 5.0 - - -
MCW800CD
115V~/60Hz - - - - - 3.0 3.5 4.0 5.0 6.0 - -
380V/3N~/50Hz - - - - - 3.0 3.5 4.0 5.0 - - -
MCW1000CD
115V~/60Hz - - - - - 3.0 3.5 4.0 5.0 6.0 - -
380V/3N~/50Hz - - - - - 3.0 3.5 4.0 5.0 6.0 7.0 8.0
MCW1200CD
115V~/60Hz - - - - - 3.0 3.5 4.0 5.0 6.0 7.0 8.0
Page 5