Specifications
2 Pipes System Specification ( 220V ~ 240 V- 50 Hz)
Model MCW200C MCW300C MCW400C MCW600C MCW800C MCW1000C MCW1200C
High m
3
/h 410 550 770 1060 1450 1640 2070
Medium m
3
/h 340 420 520 850 1180 1360 1760
Air flow
Low m
3
/h 230 350 390 710 920 1100 1510
W 1500 2300 2850 4400 5410 6240 8010
Total
Btu/h 5110 7840 9720 15010 18450 21290 27330
W 3680 5200 7450 10060 13200 14900 19370
Cooling
Capacity
Sensible
Btu/h 12550 17740 25420 34320 45040 50840 66090
Heating Capacity W 2240 3300 4450 6220 7900 9120 10810
Water Flow l/min(m
3
/hr) 7(0.41) 10(0.57) 13(0.78) 19(1.08) 24(1.39) 26(1.56) 32(1.92)
Head Loss kPa 14.6 12.0 21.6 38.2 18.4 21.0 32.7
Fan
Type Centrifugal fan (forward-curved galvanized steel fan wheels)
Number of Fans 1 1 2 2 3 3 4
Fan Housing Galvanized steel
Coil
Type Seamless copper tube mechanically bonded to configurated aluminium fin
Routine Testing Pressure Pressure test: 3.0MPa for 1 minute; leakage test: 1.6MPa for 5 minutes
Motor
Type Split-capacitor motor with ball bearing
Number of Motors 1 1 1 1 2 2 2
Rated Voltage 220-240V~
Rated Frequency 50Hz
0 Pa
W
22 33 45 65 100 105 133
Rated Input 30 Pa
W
27 58 74 120 165 177 237
power 60 Pa
W
41 65 83 140 197 215 280
80 Pa
W
44 79 85 148 200 220 283
Insulation Class E
Pipe Connection Rc3/4
Drain Pipe R 3/4
Length mm 714 884 1014 1214 1464 1564 1824
Width mm 490 (without Plenum) / 556 ( with Plenum)
Dimension
Height mm 251
Net Weight kg 19 22 26 30 41 44 46
Net Weight (Plenum) kg 20 23 28 33 44 48 50
Conditions:
Cooling Capacity: Entering air temp.27 (DB*),19.5(WB**); Entering water temp. 7ºC, Leaving water temp. 12ºC
Heating Capacity: Entering air temp. 21(DB); Entering water temp. 60ºC, the same amount of water flow with cooling.
Air Flow: Under dry coil conditions, fan speed high weight: Not include packing
* DB: Dry Bulb **WB: Wet Bulb
Note: The suggested range of the entering water temperature is 5-10 while cooling. To make sure the unit run normally for long
time, the entering water temperature should not be more than 60. Water pressure of the unit should not be more than 1.3MPa.