2 Pipes System Specification ( 115 V- 60 Hz)
Model MCW200C MCW300C MCW400C MCW600C MCW800C MCW1000C MCW1200C
High m
3
/h 408 595 765 1138 1427 1699 2175
Medium m
3
/h 306 459 663 901 1155 1308 1750
Air flow
Low m
3
/h 204 340 510 731 952 1054 1444
W 1500 2300 2850 4400 5410 6240 8010
Total
Btu/h 5110 7840 9720 15010 18450 21290 27330
W 3680 5200 7450 10060 13200 14900 19370
Cooling
Capacity
Sensible
Btu/h 12550 17740 25420 34320 45040 50840 66090
Heating Capacity W 2240 3300 4450 6220 7900 9120 10810
Water Flow l/min(m
3
/hr) 7(0.41) 10(0.57) 13(0.78) 19(1.08) 24(1.39) 26(1.56) 32(1.92)
Head Loss kPa 14.6 12.0 21.6 38.2 18.4 21.0 32.7
Fan
Type Centrifugal fan (forward-curved galvanized steel fan wheels)
Number of Fans 1 1 2 2 3 3 4
Fan Housing Galvanized steel
Coil
Type Seamless copper tube mechanically bonded to configurated aluminium fin
Routine Testing Pressure Pressure test: 3.0MPa for 1 minute; leakage test: 1.6MPa for 5 minutes
Motor
Type Split-capacitor motor with ball bearing
Number of Motors 1 1 1 1 2 2 2
Rated Voltage 115V~
Rated Frequency 60Hz
Rated Input 60 Pa W 63 97 111 183 263 281 357
power 80 Pa W 67 104 117 187 265 285 357
Insulation Class E
Pipe Connection Rc3/4
Drain Pipe R 3/4
Length mm 714 884 1014 1214 1464 1564 1824
Width mm 490 (without Plenum) / 556 ( with Plenum)
Dimension
Height mm 251
Net Weight kg 19 22 26 30 41 44 46
Net Weight (Plenum) kg 20 23 28 33 44 48 50
Conditions:
Cooling Capacity: Entering air temp.26.7DB*),19.4(WB**); Entering water temp. 7℃, Leaving water temp. 12℃
Heating Capacity: Entering air temp. 21℃(DB); Entering water temp. 60℃, the same amount of water flow with cooling.
Air Flow: Under dry coil conditions, fan speed high weight: Not include packing
* DB: Dry Bulb **WB: Wet Bulb
Note: The suggested range of the entering water temperature is 5℃-10℃ while cooling. To make sure the unit run normally for long
time, the entering water temperature should not be more than 60℃. Water pressure of the unit should not be more than 1.3MPa
Page 7