McQuay IM 777-4 27
Service and Maintenance
Figure 39: Drive Belt Adjustment
WARNING
Moving belt and fan can cause severe personal injury or
death. During installation and filter maintenance:
Verify that the belt and fan guards on plenum fan units are
always in place.
Lock and tag out fans to prevent accidental start up.
Do not enter the filter compartment until the fan is
completely stopped.
Use approved equipment for reaching filters located above
normal reach. Do not step on filter frames or unit
components.
Floor surfaces must be dry and free of oil or grease.
B
e
l
t
s
p
a
n
Deflection =
Belt span
64
WARNING
Pendant l’installation et où l’entretien des filtres, une courroie
en mouvement ou un ventilateur en opération peuvent causer
des blessures graves où même causer la mort.
S’assurer que les gardes de courroie et de ventilateur sont
toujours en place.
Verouiller les démarreurs des ventilateurs et afficher un avis
de mise-en-garde afin de prévenir tout accident ou
démarrage.
Attendre que le ventilateur soit complètement arrêté avant
d’entrer dans l’unité.
Utiliser seulement des équipements approuvé pour joindre
les bancs de filtres; ne pas mettre soit sur les cadres des
filtres ou même sur toutes composantes de l’unité.
La surface des planchers doit être sec et libre de toute trace
d'huile et où de graisse.
Table 18: Belt Deflection Force (per Browning
®
specifications)
Cross
section
Sheave diameter (in) Deflection force (lbs)
Smallest
sheave
diameter range
rpm
range
Cross section A, B, 5V Cross section AX, BX, 5VX
Used belt New belt Used belt New belt
A, AX
3.0 to 3.6
1000 to 2500 3.7 5.5 4.1 6.1
2501 to 4000 2.8 4.2 3.4 5.0
3.8 to 4.8
100 to 2500 4.5 6.8 5.0 7.4
2501 to 4000 3.8 5.7 4.3 6.4
5.0 to 7.0
1000 to 2500 5.4 8.0 5.7 9.4
2501 to 4000 4.7 7.0 5.1 7.6
B, BX
3.4 to 4.2
850 to 2500 4.9 7.2
2501 to 4000 4.2 6.2
4.4 to 5.6
860 to 2500 5.3 7.9 7.1 10.5
2501 to 4000 4.5 6.7 7.1 9.1
5.8 to 8.6
860 to 2500 6.3 9.4 8.5 12.6
250 to -4000 6.0 8.9 7.3 10.9
5V, 5VX
4.4-6.7
500-1749 10.2 15.2
1750-3000 8.8 13.2
3001-4000 5.6 8.5
7.1-10.9
500-1740 12.7 18.9 14.8 22.1
1741-3000 11.2 16.7 13.7 20.1
11.8-16.0
500-1740 15.5 23.4 17.1 25.5
1741-3000 14.6 21.8 16.8 25.0