MCAC-2008-11 Air-cooled Modular Chiller
6
4. Specification
For fix speed heat pump 30kW module:
MGA-F( )W/SN1
Model
30 60 90 120 150 180 210 240
Combination (Main module + auxiliary module) Pieces 1+0 1+1 1+2 1+3 1+4 1+5 1+6 1+7
Cooling Capacity kW 30 60 90 120 150 180 210 240
Heating Capacity kW 32 64 96 128 160 192 224 256
Power supply V/Ph/Hz 380-415/3/50
Type Scroll (fixed speed)
Compressor
Quantities Pieces 2 4 6 8 10 12 14 16
Cooling kW 10 20 30 40 50 60 70 80
Power input
Heating kW 9.8 19.5 29.3 39 48.8 58.5 68.3 78
Type R410A
Refrigerant
Weight kg 7 7×2 7×3 7×4 7×5 7×6 7×7 7×8
Air side heat-exchanger type Copper-fin-coil
Quantities of fan motor Pieces 1 2 3 4 5 6 7 8
Air flow volume ×10
3
m
3
/h 12 24 36 48 60 72 84 96
Condenser
(Air side)
Fan motor input kW 0.7 0.7×2 0.7×3 0.7×4 0.7×5 0.7×6 0.7×7 0.7×8
Water side heat-exchanger type Plate type
Water resistance loss kPa 18 18 18 18 18 18 18 18
Water inlet/outlet pipeline diameter mm 133 133 133 133 133 133 133 133
Water flow volume m
3
/h 5.2 10.3 15.5 20.6 25.8 30.9 36 41.2
Max. Pressure MPa 1 1 1 1 1 1 1 1
Evaporator
(Water side)
Water pipe connection type Soft connection
L mm 1514 1514 1514 1514 1514 1514 1514 1514
W mm 850 2300 3750 5200 6650 8100 9550 11000
Dimension
H mm 1820 1820 1820 1820 1820 1820 1820 1820
Packing size L×W×H mm 1620×1034×2041
Net weight kg 440 880 1320 1760 2200 2640 3080 3520
Weight
Operating weight kg 470 940 1410 1880 2350 2820 3290 3760
Power wiring mm
2
×No. 10×5-core Connection
wiring
Signal wiring mm
2
×No. 0.75×3-core
Control type Wired controller
Safety protection device
High/low-pressure switch, anti-frost protection, water-flow switch, over-load
protection, and power phases sequence protection.
Power supply V/Ph/Hz 380/3/50 Electric
heater
(optional)
Power input W 7.5 15 22.5 30 37.5 45 52.5 60
Noise level dB(A) 58
Operation water temp ℃ Cooling:5~17 Heating:45~50
Ambient temp ℃ Cooling:17~48 Heating:-10~21
Note: Please refer to the water flow volume in the above table strictly to design and install.