MLCAC-UTSM-2010-10 The Specification of Power
Ceiling & Floor Type 57
9. The Specification of Power
Model 12000Btu/h 18000-30000Btu/h
36000-60000
Btu/h
30000-60000
Btu/h
INDOOR UNIT
POWER
Phase 1-phase 1-phase 1-phase 1-phase
Frequency and
Voltage
220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz
POWER WIRING
(mm
2
)
3×1.5 3×1.0 3×1.0 3×1.0
CIRCUIT BREAKER
(A)
20 15 15 15
OUTDOOR UNIT
POWER
Phase 1-phase 1-phase 3-phase
Frequency and
Voltage
220-240V, 50Hz 220-240V, 50Hz 380-420V, 50Hz
POWER WIRING
(mm
2
)
3×2.5 3×4.0 5×2.5
CIRCUIT BREAKER
(A)
30 40 40
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
4×1.5 3×0.5 3×0.5 3×0.5
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)