MCAC-VTSM-2015-10 R410A All DC Inverter V5 X Series 50Hz
Installation 101
copper shavings from entering the pipe.
2) After the chamfering is completed, use veiling to remove the copper chip out of the pipe.
3) Ensure piping is not scarred, so as to avoid any breaches during flaring.
4) If the pipe end is deformed, cut the end off and then cut the pipe again.
4.3.3 Pipe expansion
1. Purpose: Expand the opening of the pipe so that another copper pipe can be inserted, serves as an
alternative to direct connections and reduces welding spots.
2. Attention: Ensure that the connection part is smooth and even; after cutting the pipe off, remove the inner
spurs.
3. Operation method: Insert the expanding head of the pipe expander into the pipe. After completing pipe
expansion, rotate the copper pipe a few degrees to rectify the straight line mark embedded by the expanding
head.
Brazing welding
4.3.4 Bell-mouthed opening
1. Purpose: Flaring bell-mouthed opening is used for screw thread connection.
2. Attention::
1) Before performing the bell-mouthed opening operation, perform fire annealing for the hard pipe.
2) Use a pipe cutter to cut pipe ensuring even cross sections and avoid refrigerant leakage; do not use a steel
saw or metal cutting device to cut pipe, in order to avoid deformation and prevent shavings from entering the
pipe.
3) Remove burrs carefully to avoid scars on the bell-mouthed opening, which may lead to refrigerant leakage.
4) When connecting pipes, use two spanners (one torque wrench and one non-adjustable spanner).
5) Before conducting opening bell-mouthed, install pipe onto the flaring nut.
6) Use proper torque to tighten the flaring nut..
Pipe Diameter
(mm)
Torque
Legend
(kgf-cm)
(N-cm)
6. 35
144~176
1420~1720
9. 53
333~407
3270~3990
12. 7
504~616
4950~6030
15. 9
630~770
6180~7540
19. 1
990~1210
9270~11860
Caution: When you are tightening the flaring nut with a spanner, the tightening torque will be suddenly increased at a
certain point. From this point, further tighten the flaring nut to the angles shown below.
Pipe Diameter
(mm)
Angle of further tightening
Recommended length of tool lever
(mm)
9. 53
60°~90°
About 200
12. 7
30°~60°
About 250
15. 9
30°~60°
About 300
Spanner
Tubing tie-in
Torque spanner
Flaring opening nut

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V5 X VRF Series and is the answer not in the manual?

Midea V5 X VRF Series Specifications

General IconGeneral
BrandMidea
ModelV5 X VRF Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals