The number of connected indoor units is 5 and the maximum number of connected indoor units on the 10HP outdoor
unit is 16, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor unit:
a) The sum of the indoor unit CIs is 314 and the CI of the 10HP outdoor unit (MVi-280WV2RN1(A)) is 280, so the
combination ratio is 314 / 280 = 112%.
b) Using the outdoor unit’s cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.10 and 1-5.11.