28
10-2. R.V. COIL CONTROL
Heating
.................
ON
Cooling
.................
OFF
Dry
....................
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds 15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
10-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
10-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V. coil
Indoor fan
motor
Defrost
heater
Discharge temperature
thermistor
Protection
○ ○
Indoor coil temperature
thermistor
Cooling: Coil frost prevention
○
Heating: High pressure protec-
tion
○ ○
Defrost thermistor Heating: Defrosting
○ ○ ○ ○ ○
Fin temperature thermistor Protection
○ ○
Ambient temperature
thermistor
Cooling: Low ambient tempera-
ture operation
○ ○ ○
Heating: Defrosting (Heater)
○
Outdoor heat exchanger tem-
perature thermistor
Cooling: Low ambient tempera-
ture operation
○ ○ ○
Cooling: High pressure protec-
tion
○ ○ ○
ACTUATOR CONTROL
10
MUZ-BT20VG MUZ-BT25VG MUZ-BT35VG MUZ-BT50VG