EasyManuals Logo

Mitsubishi Heavy Industries FDT100VNAWVH User Manual

Mitsubishi Heavy Industries FDT100VNAWVH
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
'19 • PAC-SM-309
-
90
-
None
Louver motor failure
(FDT, FDTC, FDE series)
Keepsashing
Stays OFF
Keepsashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
NO
YES
Is LM wiring
broken?
Is LM locked?
Check at the indoor unit side.
LM: louver motor
Is the louver
operable with the remote
control?
YES
NO
Does the louver
operate at the power
on?
YES
NO
YES
NO
Operate after
waiting for more
than 1 minute.
Repair wiring.
Defective indoor unit control
PCB
Replace.
Replace LM.
Normal
Adjust LM lever and then
check again.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Defective LM
LM wire breakage
Faulty indoor unit control PCB
Note:
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content

Table of Contents