Refrigerant Piping Information
RAC CURRENT MODELS
Model Precharged Maximum Maximum Vertical Factory Additional Pipe Sizes MCB
Piping Piping Piping Length (m) Charge Charge R410A Liquid Pipe Gas Pipe Rating
Length (m) Length (m) O/D Above I/D Above R410A (kg) per m (g/m) "" (mm) "" (mm) A
SRC25ZMP-S, 10 15 10 10 0.655 20 1/4" (6.35) 3/8" (9.52) 16
SRC35ZMP-S 15 15 10 10 0.810 N/A 1/4" (6.35) 3/8" (9.52) 16
SRC45ZMP-S 15 25 15 15 1.200 20 1/4" (6.35) 1/2" (12.7) 16
SRC25ZM-S 15 15 10 10 0.750 N/A 1/4" (6.35) 3/8" (9.52) 16
SRC35ZM-S 15 15 10 10 1.050 N/A 1/4" (6.35) 3/8" (9.52) 16
SRC50ZM-S 15 25 15 15 1.350 20 1/4" (6.35) 1/2" (12.7) 16
FDC100VNP 15 30 20 20 2.550 60 3/8" (9.52) 5/8" (15.88) 32
SRC20_35ZMX-S 15 15 10 10 1.200 N/A 1/4" (6.35) 3/8" (9.52) 16
SRC50_60ZMX-S 15 30 20 20 1.500 20 1/4" (6.35) 1/2" (12.7) 16
SRC63ZR-S 15 30 20 20 1.550 20 1/4" (6.35) 1/2" (12.7) 16
SRC71ZR-S 15 30 20 20 1.800 25 1/4" (6.35) 5/8" (15.88) 20
SRC80ZR-S 15 30 20 20 1.900 25 1/4" (6.35) 5/8" (15.88) 20
SRC20_25ZS-S 15 20 10 10 0.750 20 1/4" (6.35) 3/8" (9.52) 16
SRC35ZS-S 15 20 10 10 0.950 20 1/4" (6.35) 3/8" (9.52) 16
SRC50ZS-S 15 25 15 15 1.250 20 1/4" (6.35) 1/2" (12.7) 20
SCM Multi Splits
For SCM Systems the maximum one way piping length to an indoor unit is 25 metres.
Model Precharged Maximum Maximum Vertical Factory Additional Pipe Sizes MCB
Piping Piping Piping Length (m) Charge Charge R410A Liquid Pipe Gas Pipe Rating
Length (m) Length (m) O/D Above I/D Above R410A (kg) per m (g/m) "" (mm) "" (mm) A
SCM40ZS-S 30 30 15 15 1.900 N/A 2x 1/4" (6.35) 2x 3/8" (9.52) 25
SCM45ZS-S 30 30 15 15 1.900 N/A 2x 1/4" (6.35) 2x 3/8" (9.52) 25
SCM50ZS-S 40 40 15 15 2.500 N/A 3x 1/4" (6.35) 3x 3/8" (9.52) 25
SCM45ZM-S 30 30 15 15 2.000 N/A 2x 1/4" (6.35) 2x 3/8" (9.52) 25
SCM60ZM-S 40 40 15 15 2.500 N/A 3x 1/4" (6.35) 3x 3/8" (9.52) 25
SCM80ZM-S 40 70 20 20 3.150 20 4x 1/4" (6.35) 4x 3/8" (9.52) 25
SCM100_125ZM-S 50 90 20 20 6.000 20 5x 1/4" (6.35) 5x 3/8" (9.52) 32
PAC Splits - CURRENT MODELS
Model Precharged Maximum Maximum Vertical Factory Additional Pipe Sizes MCB
Piping Piping Piping Length (m) Charge Charge R410A Liquid Pipe Gas Pipe Rating
Length (m) Length (m) O/D Above I/D Above R410A (kg) per m (g/m) "" (mm) "" (mm) A(/ph)
FDC71VNP 15 30 20 20 1.600 20 1/4" (6.35) 1/2" (12.7) 20
FDC90VNP 15 30 20 20 2.100 20 1/4" (6.35) 5/8" (15.88) 20
FDC100VNP 15 30 20 20 2.550 60 3/8" (9.52) 5/8" (15.88) 32
FDC100VN 30 50 30 15 3.800 60 3/8" (9.52) 5/8" (15.88) 32
FDC125VN 30 50 30 15 3.800 60 3/8" (9.52) 5/8" (15.88) 32
FDC140VN 30 50 30 15 3.800 60 3/8" (9.52) 5/8" (15.88) 32
FDC71VNX 30 50 30 15 2.950 60 3/8" (9.52) 5/8" (15.88) 25
FDC100VNX 30 100 30 15 4.500 60 3/8" (9.52) 5/8" (15.88) 32
FDC125VNX 30 100 30 15 4.500 60 3/8" (9.52) 5/8" (15.88) 32
FDC140VNX 30 100 30 15 4.500 60 3/8" (9.52) 5/8" (15.88) 32
FDC100VS 30 50 30 15 3.800 60 3/8" (9.52) 5/8" (15.88) 20
FDC125VS 30 50 30 15 3.800 60 3/8" (9.52) 5/8" (15.88) 20
FDC140VS 30 50 30 15 3.800 60 3/8" (9.52) 5/8" (15.88) 20
FDC100VSX 30 100 30 15 4.500 60 3/8" (9.52) 5/8" (15.88) 20
FDC125VSX 30 100 30 15 4.500 60 3/8" (9.52) 5/8" (15.88) 20
FDC140VSX 30 100 30 15 4.500 60 3/8" (9.52) 5/8" (15.88) 20
FDC200VSA 30 70 30 15 5.600 60 3/8" (9.52) 7/8" (22.22) 32
FDC250VSA 30 70 30 15 7.200 120 1/2" (12.7) 1-1/8" (28.58) 32

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SRF-ZMX-S and is the answer not in the manual?

Mitsubishi Heavy Industries SRF-ZMX-S Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSRF-ZMX-S
CategoryAir Conditioner
LanguageEnglish

Related product manuals