If no data is recorded (error code is normal), the information display in the remote control becomes as follows.
•
EXAMPLE - Outdoor air sensor temperature “42 ºC”
When the temperature value is ≧0, the buzzer does not sound. Run light x4 flashes and Timer light flashes twice.
BUZZER Off
RUN LIGHT
TIMER LIGHT
No Buzzer, Run light x 4, Timer light x 2.
Buzzer sound Run light
Timer Light (1’s digit)
(10’s digit)
0 1 2 3 4 5 6 7 8 9
6 -60 -61 -62 -63 -64
5 -50 -51 -52 -53 -54 -55 -56 -57 -58 -59
4 -40 -41 -42 -43 -44 -45 -46 -47 -48 -49
Yes 3 -30 -31 -32 -33 -34 -35 -36 -37 -38 -39
(sounds for 0.1 second) 2 -20 -21 -22 -23 -24 -25 -26 -27 -28 -29
1 -10 -11 -12 -13 -14 -15 -16 -17 -18 -19
0 0 -1 -2 -3 -4 -5 -6 -7 -8 -9
0 0 1 2 3 4 5 6 7 8 9
1 10 11 12 13 14 15 16 17 18 19
2 20 21 22 23 24 25 26 27 28 29
3 30 31 32 33 34 35 36 37 38 39
No 4 40 41 42 43 44 45 46 47 48 49
(does not sound) 5 50 51 52 53 54 55 56 57 58 59
6 60 61 62 63 64 65 66 67 68 69
7 70 71 72 73 74 75 76 77 78 79
8 80 81 82 83 84 85 86 87 88 89
9 90 91 92 93 94 95 96 97 98 99
Room temperature sensor, indoor heat exchanger sensor, outdoor air temperature sensor, outdoor heat exchanger sensor.
Buzzer sound Run light
Timer Light (1’s digit)
(10’s digit)
0 1 2 3 4 5 6 7 8 9
Yes 2 -40 -42 -44 -46 -48 -50 -52 -54 -56 -58
(sounds for 0.1 second) 1 -20 -22 -24 -26 -28 -30 -32 -34 -36 -38
0 0 -2 -4 -6 -8 -10 -12 -14 -16 -18
0 0 2 4 6 8 10 12 14 16 18
1 20 22 24 26 28 30 32 34 36 38
2 40 42 44 46 48 50 52 54 56 58
No 3 60 62 64 66 68 70 72 74 76 78
(does not sound) 4 80 82 84 86 88 90 92 94 96 98
5 100 102 104 106 108 110 112 114 116 118
6 120 122 124 126 128 130 132 134 136 138
7 140 142 144 146 148 150
Sensor name Sensor value displayed when the error code is normal
Room temperature sensor -64ºC
Indoor heat exchanger sensor -64ºC
Outdoor air temperature sensor -64ºC
Outdoor heat exchanger sensor -64ºC
Discharge pipe sensor -64ºC