Page #37 background imageLoading...
Page #37 background image
If no data is recorded (error code is normal), the information display in the remote control becomes as follows.
EXAMPLE - Outdoor air sensor temperature “42 ºC”
When the temperature value is 0, the buzzer does not sound. Run light x4 flashes and Timer light flashes twice.
BUZZER Off
RUN LIGHT
TIMER LIGHT
No Buzzer, Run light x 4, Timer light x 2.
Buzzer sound Run light
Timer Light (1’s digit)
(10’s digit)
0 1 2 3 4 5 6 7 8 9
6 -60 -61 -62 -63 -64
5 -50 -51 -52 -53 -54 -55 -56 -57 -58 -59
4 -40 -41 -42 -43 -44 -45 -46 -47 -48 -49
Yes 3 -30 -31 -32 -33 -34 -35 -36 -37 -38 -39
(sounds for 0.1 second) 2 -20 -21 -22 -23 -24 -25 -26 -27 -28 -29
1 -10 -11 -12 -13 -14 -15 -16 -17 -18 -19
0 0 -1 -2 -3 -4 -5 -6 -7 -8 -9
0 0 1 2 3 4 5 6 7 8 9
1 10 11 12 13 14 15 16 17 18 19
2 20 21 22 23 24 25 26 27 28 29
3 30 31 32 33 34 35 36 37 38 39
No 4 40 41 42 43 44 45 46 47 48 49
(does not sound) 5 50 51 52 53 54 55 56 57 58 59
6 60 61 62 63 64 65 66 67 68 69
7 70 71 72 73 74 75 76 77 78 79
8 80 81 82 83 84 85 86 87 88 89
9 90 91 92 93 94 95 96 97 98 99
SENSOR TABLE
Room temperature sensor, indoor heat exchanger sensor, outdoor air temperature sensor, outdoor heat exchanger sensor.
Buzzer sound Run light
Timer Light (1’s digit)
(10’s digit)
0 1 2 3 4 5 6 7 8 9
3 -60 -62 -64
Yes 2 -40 -42 -44 -46 -48 -50 -52 -54 -56 -58
(sounds for 0.1 second) 1 -20 -22 -24 -26 -28 -30 -32 -34 -36 -38
0 0 -2 -4 -6 -8 -10 -12 -14 -16 -18
0 0 2 4 6 8 10 12 14 16 18
1 20 22 24 26 28 30 32 34 36 38
2 40 42 44 46 48 50 52 54 56 58
No 3 60 62 64 66 68 70 72 74 76 78
(does not sound) 4 80 82 84 86 88 90 92 94 96 98
5 100 102 104 106 108 110 112 114 116 118
6 120 122 124 126 128 130 132 134 136 138
7 140 142 144 146 148 150
SENSOR TABLE
Discharge Pipe Sensor
Sensor name Sensor value displayed when the error code is normal
Room temperature sensor -64ºC
Indoor heat exchanger sensor -64ºC
Outdoor air temperature sensor -64ºC
Outdoor heat exchanger sensor -64ºC
Discharge pipe sensor -64ºC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SRF-ZMX-S and is the answer not in the manual?

Mitsubishi Heavy Industries SRF-ZMX-S Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSRF-ZMX-S
CategoryAir Conditioner
LanguageEnglish

Related product manuals