CC-Link Ver.1.10
FX
2N
-16CCL-M CC-Link SYSTEM MASTER BLOCK
HARDWARE MANUAL
JY992D93201B
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX
2N
-16CCL-M CC-Link SYSTEM MASTER BLOCK. It should be read and
understood before attempting to install or use the unit. Further information can be found in the FX series
PLC hardware manuals.
Note’s on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the user’s personal safety and protect the integrity of the equipment.
Whenever any of the following symbols are encountered, its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
1. INTRODUCTION
1.1 Associated Manuals
★
: Indispensable manual
✩
: Manual required depending on equipment used
Manual name Manual number Description
★
FX
2N
-16CCL-M
User’s Manual
JY992D93101
(sent separately)
Describes programming and handling of the CC-
Link master block FX
2N
-16CCL-M.
★
FX
1S
/FX
1N
/FX
2N
/FX
2NC
Programming Manual II
JY992D88101
(sent separately)
Explains the instructions in the FX
1S
/FX
1N
/FX
2N
/
FX
2NC
Series PLC.
✩
FX
1N
Hardware Manual
JY992D89301
(packed with product)
Describes the contents related to the hardware
such as specification, wiring and mounting of the
FX
1N
Series PLC.
✩
FX
2N
Hardware Manual
JY992D66301
(packed with product)
Describes the contents related to the hardware
such as specification, wiring and mounting of the
FX
2N
Series PLC.
✩
FX
2NC
Hardware Manual
JY992D76401
(packed with product)
Describes the contents related to the hardware
such as specification, wiring and mounting of the
FX
2NC
Series PLC.
✩
FX
2N
-32CCL
User’s Manual
JY992D71801
(packed with product)
Describes programming and handling of the CC-
Link interface block FX
2N
-32CCL.
1.2 Overview
The CC-Link master block FX
2N
-16CCL-M is a special extension block which assigns an FX Series PLC
as the master station of the CC-Link system.
1) Remote I/O stations and remote device stations can be connected to the master station (FX Series
PLC).
Master station : Station which controls the data link system
Remote I/O station : Remote station which handles only the 1-bit information
Remote device station : Remote station which handles both bit information and word information
2) By using the CC-Link interface block FX
2N
-32CCL, two or more FX Series PLCs can be connected as
remote device stations to configure a simple distributed system.
1.3 Dimensions and Setting
Dimensions: mm (inches) MASS (Weight): 0.4 kg (0.88 lbs)
Number Name Description
1) LED
indicators 1
LED
name
Description
LED status
Normal Error
RUN
ON : Module is normal.
OFF: Watchdog time error has occurred.
ON OFF
ERR.
Indicates the communication status with
the stations set in parameter.
ON : Communication error has
occurred in all stations.
Flashing : Communication error has
occurred in some stations.
OFF
ON or
flashing
MST ON : Set as the master station
ON OFF
TEST1 Test result indication
OFF except during test
TEST2 Test result indication
L RUN
ON : Data link is being executed
(host station).
ON OFF
L ERR.
ON : Communication error has
occurred (host station).
Flashing : The settings of the switches 4)
to 7) are changed while the
power is ON.
OFF
ON or
flashing
2) Power indictor POWER ON : 24V DC is supplied from the outside.
ON OFF
Remote I/O station
FX
1N
/FX
2N
/FX
2NC
Series PLC
CC-Link master block
FX
2N
-16CCL-M
Remote device station
Remote I/O station
Remote device station
CC-Link interface block
FX
2N
-32CCL
FX
0N
/FX
1N
/FX
2N
/FX
2NC
Series PLC
Partner manufacturer's
product
RUN
ERR.
L ERR.
L RUN
MST
TEST1
TEST2
POWER
SW
M/S
PRM
TIME
LINE
SD
RD
E
R
R
O
R
´10
´
1
STATION
NO.
MODE
B RATE
1
3
2
4
156K
625K
2.5M
5M
10M
0
HLD
--
ONOFF
SW
1
2
3
--
-
-
-
-
4
5
6
7
8
-
-
--
-
-
CLR
FX
2N
-16CCL-M
0
1
2
3
4
5
6
7
8
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
12345678
ON
RUN
ERR.
MST
TEST1
TEST2
L RUN
L ERR.
POWER
SW
M/S
PRM
TIME
LINE
SD
RD
E
R
R
O
R
85(3.34)
90(3.5)
87(3.43)
9(0.35)
FX2N-16CCL-M
2-
f
4.5
80(3.15)
75(2.95)
MITSUBISHI
1)
2)
3)
4)
5)
6)
8)
7)
9)
10)
11)
12)
Inside of top cover
24+
24-
FG
SLD DG
DA
DB
RUN
ERR.
MST
TEST 1
TEST 2
L RUN
L ERR
3) LED
indicators 2
E
R
R
O
R
SW ON : Switch setting error has occurred. OFF ON
M/S
ON : The master station is already
present in the same line.
OFF ON
PRM
ON : Parameter setting error has occurred.
OFF ON
TIME
ON : Data link watchdog timer is actuated
(error in all stations).
OFF ON
LINE
ON : The cable is broken or the
transmission route is affected by
noise, etc.
OFF ON
SD ON : Data is being transmitted.
ON OFF
RD ON : Data is being received.
ON OFF
4)
Station
number setting
switch
Sets the station number of the module. (Default setting at shipment: 00)
<Setting range>
00 (because the FX
2N
-16CCL-M is dedicated to the master station)
If "65" or larger number is set, the "SW" and "L ERR." LED indicators turn ON.
5) Mode setting
switch
Sets the operation status of the module. (Default setting at shipment: 0)
Number Name Description
0 Online Sets connection to data link.
1 (Unusable)
2 Offline Sets disconnection from data link.
3 Line test 1 Refer to USER’S MANUAL.
4 Line test 2 Refer to USER’S MANUAL.
5
Parameter
verification test
Refer to USER’S MANUAL.
6 Hardware test Refer to USER’S MANUAL.
7 (Unusable) Setting error (The SW LED indicator turns ON.)
8 to A (Unusable) Cannot be set because it is already used inside.
B to F (Unusable) Setting error (The SW LED indicator turns ON.)
6) Transmission
speed setting
switch
Sets the transmission speed of the module. (Default setting at shipment: 0)
Number Setting contents
0 156 kbps
1 625 kbps
2 2.5 Mbps
3 5 Mbps
4 10 Mbps
5 to 9 Setting error (The SW and L ERR. LED indicators turn ON.)
7) Condition
setting switch
Sets the operation condition. (Default setting at shipment: All OFF)
Number Setting description Switch status
ON OFF
SW1 to
SW3
(Unusable) Always OFF
SW4 Input data status in data link faulty station
Keep
(HLD)
Clear
(CLR)
SW5 to
SW8
(Unusable) Always OFF
8) Terminal block Connects dedicated CC-Link cables to enable data link. For the connection
method, refer to Section 2.3.
The terminals SLD and FG are connected inside.
M3.5 Screw
9) Terminal block Connects the power supply to operate the master block.
M3 Screw
10) Extension
cable
Connects the PLC.
11) Next step
extension
connector
Connects an extension equipment.
12) DIN rail
mounting
groove
DIN46277: DIN rail mounting groove of 35 mm (1.38") in width
Number Name Description
SW
M/S
PRM
TIME
LINE
SD
RD
E
R
R
O
R
STATION NO.
×
10
×
1
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
MODE
1
2
3
4
5
6
7
8
9
0
A
B
C
D
E
F
B RATE
0
2
1
3
4
156K
625K
2.5M
5M
10M
1
2
3
4
5
6
7
8
9
0
HLD
SW
ON
CLR
OFF
ON
12345678
2
1
3
4
6
5
7
8
SLD DG DA DB
24+
24-
FG
Guidelines for the safety of the user and protection of the FX
2N
-16CCL-M CC-Link
SYSTEM MASTER BLOCK
• If in doubt at any stage during the installation of the FX
2N
-16CCL-M CC-Link SYSTEM MASTER
BLOCK always consult a professional electrical engineer who is qualified and trained to the local
and national standards. If in doubt about the operation or use of the FX
2N
-16CCL-M CC-Link
SYSTEM MASTER BLOCK please consult the nearest Mitsubishi Electric distributor.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
• Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.