10
SERVICE FUNCTIONS
8
Table 1
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
2 units operation
Same as at left
Solder J1
3 units operation
Same as at left
Same as at left
Solder J2
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows. (Refer to 9-6.)
Set time : 1 minute 1-second
Set time : 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
MSH-GA50VB
MSH-GA60VB
MSH-GA80VB
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the
remote controller for the indoor unit.
The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are
set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
NOTE : For modification, take out the batteries and press the OPERATE/ STOP (ON/ OFF) button 2 or 3 times at first.
After modification, put back the batteries then press the RESET button.
Remote controller model : KM04A
J2
J1
Remote controller model : KP0A
J1
J2
OB367D-1.qxp 12.1.13 7:49 AM Page 10
OB367D
Downloaded from AC-Manual.com Manuals

Other manuals for Mitsubishi MSH-GA60VB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MSH-GA60VB and is the answer not in the manual?

Mitsubishi MSH-GA60VB Specifications

General IconGeneral
BrandMitsubishi
ModelMSH-GA60VB
CategoryAir Conditioner
LanguageEnglish

Related product manuals