EasyManuals Logo
Home>Mitsubishi>Controller>QY40P

Mitsubishi QY40P User Manual

Mitsubishi QY40P
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
2 - 29 2 - 29
MELSEC-Q
2 INPUT MODULE SPECIFICATIONS
2.22 QX81-S2 DC Input Module (Negative Common Type)
Type
Specifications
DC input module (Negative common type)
QX81-S2 Appearance
Number of input points 32 points
Isolation method Photocoupler
Rated input voltage 24VDC (+20/-15%, ripple ratio within 5%)
Rated input current Approx. 6mA
Input derating Refer to the derating chart.
ON voltage/ON current 15V or higher/3mA or higher
OFF voltage/OFF current 5V or lower/1.7mA or lower
Input impedance Approx. 3.6k
Response
time
OFF to ON
1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1
(Default: 10ms)
ON to OFF
1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1
(Default: 10ms)
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m)
Insulation resistance 10M or more by insulation resistance tester
Noise immunity
By noise simulator of 500Vp-p noise voltage, 1 s noise width
and 25 to 60Hz noise frequency
First transient noise IEC61000-4-4: 1kV
Protection degree IP2X
Common terminal arrangement 32 points/common (common terminal: 17, 18, 36)
Number of occupied I/O points 32 points (I/O assignment is set as a 32-point input module.)
Operation indicator ON indication (LED)
External connections 37-pin D-sub connector
Applicable wire size
0.088 to 0.3mm
2
(For A6CON1E) 2
Applicable connector A6CON1E, A6CON2E, A6CON3E (optional)
Applicable connector/terminal block
converter module
A6TBX36-E, A6TBX54-E, A6TBX70-E
Internal current consumption
(5VDC)
75mA (TYP. all points ON)
(0.08A is shown on the rating plate of the module.)
Weight 0.16kg
Derating chart Pin-Outs
Pin
No.
Signal
No.
Pin
No.
Signal
No.
Module front view
1 X00 9 X10
20 X01 28 X11
2 X02 10 X12
21 X03 29 X13
3 X04 11 X14
22 X05 30 X15
4 X06 12 X16
23 X07 31 X17
5 X08 13 X18
External connection
24 X09 32 X19
6 X0A 14 X1A
25 X0B 33 X1B
7 X0C 15 X1C
26 X0D 34 X1D
8 X0E 16 X1E
27 X0F 35 X1F
17 COM 37 Vacant
36 COM 19 Vacant
18 COM
1: For the setting method, refer to Section 1.3.1.
2: When using A6CON2E or A6CON3E, refer to Chapter 7.
100
90
80
70
60
50
40
0102030405055
30
20
10
ON
ratio
A
mbient temperature
( )
(%)
(31.25%) 24VDC
(18.75%) 28.8VDC
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi QY40P and is the answer not in the manual?

Mitsubishi QY40P Specifications

General IconGeneral
BrandMitsubishi
ModelQY40P
CategoryController
LanguageEnglish