128
-
'11 • SCM-SM-110
Error code
Remote controller:
LED Green Red
Indoor
Keeps flashing
Stays OFF
Content
E48
Outdoor fan motor anomaly
Outdoor
Keeps ashing
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
YES
NO
Does any
foreign material intervene
in rotational area of fan
propeller?
NO
Does the
fan rotate smoothly when turned
by hand?
NO
Is DC308~336V
detected between (CNFAN (blue)- (red))
SCM100,125: CNFAN (blue)– (red)
of fan motor connector?
Is F3 (250V1A)
ާSCM100, 125: F4 (250V4A)ި
Is normal state restored?
YES
YES
NO
YES
NO
YES
Power supply reset
Remove foreign matter.
Replace fan motor.
If resistance between
(Vm):white -
(GND)
SCM100, 125:
(Vm):
white-
(GND)
:blue is
detected 1k
Ω
or lower, it is
faulty.
Check power supply
voltage.
Replace faulty fan motor
and outdoor main PCB.
Replace fan motor (If
anomaly persists after
replacing fan motor, replace
outdoor main PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
outdoor fan motor
3.
Condition of Error displayed
When actual rotation speed
of outdoor fan motor drops to
75min
-1
or lower for 30 minutes
continuously, the compressor
and the outdoor fan motor stop.
After 3-minutes delay, it starts
again automatically, but if this
anomaly occurs 3 times within
60 minutes after the initial
detection.
4. Presumable cause
Defective outdoor main
(control) PCB
Foreign material at rotational
area of fan propeller
Defective fan motor
Dust on outdoor main
(control) PCB
Blown F3 fuse
Note: When E48 error occurs, in almost cases F3 (SCM100, 125: F4) fuse on the outdoor main (control) PCB is blown. There are a lot of cases that fuse
is blown and E48 occurs due to defective fan motor. And even though only the outdoor main (control) PCB ( or fuse) is replaced,, another trouble
could occur. Therefore when fuse is blown, check whether the fan motor is OK or not.
After conrming the fan motor normal, check by power ON. (Don't power ON without conrming the fan motor normal.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM50ZJ-S1 and is the answer not in the manual?

Mitsubishi SCM50ZJ-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSCM50ZJ-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals