1.2.5 Selection chart
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the following way.
Net capacity = Capacity shown on specificationCorrection factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling capacity in relation to the one way piping length between the indoor and outdoor units.
14 16 18 20 22
15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Cooling
Applicable range
Coefficient of cooling
capacity in relation
to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
Piping length [m]
Cooling
7
1.0
10
0.99
15
0.975
How to obtain the cooling capacity
Example : The net cooling capacity of the model SRK12CH with the piping length of 15m, indoor wet-bulb temperature at 19.0˚C and
outdoor dry-bulb temperature 35˚C is Net cooling capacity =
SRK12CH
(11213 BTU/h)
Length 15m
Factor by air
temperatures
(11500 BTU/h)
3370W 0.975
1.0
3286 W
✕✕
=

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SRK10CHV-4 and is the answer not in the manual?

Mitsubishi SRK10CHV-4 Specifications

General IconGeneral
BrandMitsubishi
ModelSRK10CHV-4
CategoryAir Conditioner
LanguageEnglish

Related product manuals