79
-
When the compressor is operating
When the compressor is stopped
(Including protection stoppage)
Inverter command speed (rps) 20 0
Indoor fan motor OFF
Outdoor fan motor 3rd Speed Determined by heating stop mode
Flap and louver Horizontal/ Center
4-way valve ON Determined by heating stop mode
(i) Fan operation1
1) Operation content
Inverter command speed (rps) 0
Indoor fan motor 2nd Speed
Outdoor fan motor OFF
Flap and louver Fully closed/ Center
(ii) Cooling operation
1) Operation content
Inverter command speed (rps) 20
Indoor fan motor 2nd Speed
Outdor fan motor 3rd Speed
Flap and louver Horizoc/Center
4-way valve OFF
Note (1) During cooling operation safety control,frost
prevention control, and cooling overload
protective control are generally not applicable
(iii) Heating cycle operation
1) Operation content
T1 T2
42min.
TimeStop
Compressor operation
2) Operation time
After cooling operation
(outdoor temperature–indoor
temperature)
T
1 (Compressor operation time)
T
2 (Compressor stopped time)
Heating operation control time (T1+T2)
–12°C
~
–10°C
80
2440
~
–12°C
90
2430
–10°C
~
–8°C
70
2450
–8°C
~
–6°C
60
2460
–6°C
~
–4°C
50
2470
42min.
–4°C
~
–2°C
40
2480
–2°C
~
0°C
30
2490
0°C
~
4°C
20
2500
4°C
~
9°C
10
2510
(Sec.)