(17) Power transistor overheat protection
(a) Purpose: In order to prevent the power transistor overheating during operation, faulty controller operations, deterioration,
damage and so on occurs.
(b) Detail of operation:
1 Power transistor sensor temperature
=
>
110°C
The compressor is stopped immediately. When the power transistor sensor temperature is less than 80°C, restart.
2 90°C
=
<
Power transistor sensor temperature < 110°C
The outdoor unit speed drops to 4 rps. After 20 seconds, the outdoor unit speed performs the following controls, according
to the power thansistor sensor temperature.
3 80°C
=
<
Power transistor sensor temperature < 90°C
Maintain the outdoor unit speed. When the rotation speed is the same for 6 minutes, or when the power transistor sensor
temperature is less than 80°C. The speed is raised by 2rps and kept at that speed for 1 minute. This process is repeated
until the inverter command speed is reached.
If the previous sensor temperature
<
=
current sensor temperature reduce by 4rps
If the previous sensor temperature > current sensor temperature reduce by 2rps
Notes (1) When the discharge pipe temperature is in the range of 100 to 110°C, the speed is reduced by 4 rps.
(2) When the discharge pipe temperature is raised and continues operation for 20 seconds without changing, then the speed is reduced again by 4 rps.
(3) If the discharge pipe temperature is still 90 °C or greater but less than 100 °C even when the inverter command speed is maintained for 3 minutes
when the temperature is 90 °C or greater but less than 100 °C, the speed is raised by 1 rps and kept at that speed for 3 minutes. This process is
repeated until the calculated speed is reached.
2) If the temperature of 110°C is detected by the sensor on the discharge pipe, then the compressor will stop immediately.
When the discharge pipe temperature drops and the time delay of 3 minutes is over, the unit starts again within 1 hour but
there is no start at the third time.
(19) Serial signal transmission error protection
(a) Purpose: Prevents malfunction resulting from error on the indoor outdoor signals.
(b) Detail of operation: If the compressor is operating and a serial signal cannot be received from the indoor control with
outdoor control having serial signals continuously for 1 minute and 55 seconds, the compressor is
stopped.
After the compressor has been stopped, it will be restarted after the compressor start delay if a serial
signal can be received again from the indoor control.
(RUN light: ON, TIMER light: 6 times flash)
(18) Compressor overheat protection
(a) Purpose: It is designed to prevent deterioration of oil, burnout of motor coil and other trouble resulting from the compressor
overheat.
(b) Detail of operation
1) Speeds are controlled with temperature detected by the sensor mounted on the discharge pipe.
Discharge pipe temperature (˚C)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
4 rps
4 rps
(1)
0 rps
(Example) Fuzzy
90 100 110
Lower limit
speed 20rps
Cooling Heating
Lower limit speed 20rps 20rps

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SRK63ZEA-S1 and is the answer not in the manual?

Mitsubishi SRK63ZEA-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSRK63ZEA-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals