61
-
Outdoor fan motor error
[Defective fan motor, connector
poor connection, defective PCB]
Is connector connection good?
YES
NO
NO
Is the output of the outdoor unit’s
printed circuit board normal?
Normal
NO
YES
YES
Correct connector connection
Is DC fan motor resistance value good?
Replace outdoor PCB
Replace outdoor fan motor
* Disconnect the fan motor
connector, then investigate
the DC fan motor and
outdoor unit circuit board
separately.
Rotor lock
[Compressor defect, outdoor
unit circuit defect]
NO
YES
¡ Check compressor wiring visually.
¡ Check insulation resistance. (1 M or over)
¡ Check coil wire resistance. (Few )
Is output voltage applied to all 3
phases of power transistor?
Inspect compressor.
Defective inverter
If check results are normal,
compressor is locked.
1 Humidity sensor operation
Failure mode Control input circuit reading
Air conditioning system operation
1 Disconnected wire Humidity reading is 0% Operates in the Dry region
2 Disconnected wire Humidity reading is 0% Operates in the Dry region
12 Disconnected wire Humidity reading is 0% Operates in the Dry region
1 and 2 are short
Humidity reading is 100% Operates in the Cooling region.
circuited
Disconnected
wire
Short
Circuit
Remark: Do not perform a continuity check of the humidity sensor with a tester. If DC current is applied, it
could damage the sensor.
Humidity sensor
element
Connector
(CnF)
Humidity sensor assembly
(8) Phenomenon observed after shortcircuit, wire breakage on sensor
(a) Indoor unit
Phenomenon
Sensor
Shortcircuit Broken wire
Cooling Release of continuous compressor operation command
Heating Continuous compressor operation command is not released.
Compressor stop.
Cooling
(Abnormality of outdoor unit)
Heating High pressure control mode
Humidity Sensor
Cooling 1 in the table below.
Heating Normal system operation is possible.
Operation
mode
Room temperature
sensor
Continuous compressor operation command is not released.
Release of continuous compressor operation command
Continuous compressor operation command is not released.
(Anti-frosting)
Hot keep (Indoor fan stop)
1 in the table below.
Heat exchanger
sensor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SRK63ZEA-S1 and is the answer not in the manual?

Mitsubishi SRK63ZEA-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSRK63ZEA-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals