Troubleshooting 27
7.7 EL 0C (Refrigerant Leakage Detection diagnosis and solution)
Description: Define the evaporator coil temperature T2 of the compressor just starts running as Tcool.
In the beginning 5 minutes after the compressor starts up, if T2< Tcool-1°C(1.8°F) does not keep continuous 4 seconds
and compressor running frequency higher than 50Hz does not keep for 3 minutes, and this situation happens 3 times,
the LED displays the failure code and AC turns off.
Recommended parts to prepare:
T2 sensor
Indoor PCB
Additional refrigerant
Troubleshooting and repair:
Power off, then restart the unit 2 minutes later.
Are any leakages
present?
Check System for blockages and
clear blockages if present.
Does a problem remain?
Put your hands in front of the
indoor air outlet.
YES
Is there cool
air blowing out from
indoor air outlet?
Is it securely
attached?
Replace the
indoor PCB
YES
Check the T2 sensor.
YES
Check system for leakages.
NO
NO
Repair the leakage and
recharge the refrigerant.
YES
NO

Other manuals for MrCool DIY E Star Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MrCool DIY E Star Series and is the answer not in the manual?

MrCool DIY E Star Series Specifications

General IconGeneral
BrandMrCool
ModelDIY E Star Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals