Troubleshooting 22
2.Field Maintenance
Possible causes of trouble
Compressor stuck
Shortage of refrigerant
Restricted liquid line
Dirty air filter
Dirty evaporator coil
Insufficient air through evaporator coil
Overcharge of refrigerant
Dirty or partially blocked condenser
Air or incompressible gas in refrigerant cycle
Short cycling of condensing air
High temperature condensing medium
Insufficient condensing medium
Broken compressor internal parts
Inefficient compressor
Expansion valve obstructed
Expansion valve or capillary tube closed completely
Leaking power element on expansion valve
Poor installation of feeler bulb
Heavy load condition
Loosen hold down bolts and / or screws
Shipping plates remain attached
Poor choices of capacity
Contact of piping with other piping or external plate
Unit will not start
Compressor will not start but fans run
Compressor and condenser (outdoor) fan will not
start
Evaporator (indoor) fan will not start
Condenser (Outdoor) fan will not start
Unit runs, but shortly stops
Compressor short-cycles due to overload
High discharge pressure
Low discharge pressure
High suction pressure
Low suction pressure
Unit runs continuously but insufficient cooling
Too cool
Compressor is noisy
Horizontal louver can not revolve
Test method / remedy
Replace the compressor
Leak test
Replace restricted part
Clean or replace
Clean coil
Check fan
Change charged refrigerant volume
Clean condenser or remove obstacle
Purge, evacuate and recharge
Remove obstruction to air flow
Remove obstruction in air or water flow
Remove obstruction in air or water flow
Replace compressor
Test compressor efficiency
Replace valve
Replace valve
Replace valve
Fix feeler bulb
Check heat load
Tighten bolts or screws
Remove them
Choose AC of lager capacity or add the number of AC
Rectify piping so as not to contact each other or with external
plate
Refrigerant Circuit
Others

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MrCool DIY-MULTI4-36HP230C and is the answer not in the manual?

MrCool DIY-MULTI4-36HP230C Specifications

General IconGeneral
BrandMrCool
ModelDIY-MULTI4-36HP230C
CategoryAir Conditioner
LanguageEnglish

Related product manuals