NAPCO StarLink Fire: Getting Started Guide 17
333 Bayview Avenue
Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at
http://tech.napcosecurity.com/
(Note: Technical Service is for security professionals only)
Publicly traded on NASDAQ Symbol: NSSC
© NAPCO 2017
The NAPCO SLECDMA-CFB-PS Commercial Fire radio, fully compliant with the 2013 edition of NFPA 72, is ap-
proved as a fire alarm communicator. The capability of indicating and communicating signal failures to the central station
within 60 minutes of an outage allows the SLECDMA-CFB-PS to replace existing telephone lines.
The following testing guide is intended to assist with the AHJ inspection of a SLECDMA-CFB-PS Fire radio installation.
All required testing procedures are described, followed by the correct system responses. Ensure that in cases where a ra-
dio trouble output is connected to an input on the FACP, the fire control panel properly annunciates the trouble condition.
Normal LED Indications
With the SLECDMA-CFB-PS in standby mode, ensure the LEDs display as follows:
AC Failure Test
Remove radio AC power and observe the following SLEULPS-R power supply indications:
Restore radio AC power:
No Battery / Low Battery Test
Disconnect the radio battery and observe the following SLEULPS-R power supply indications:
Reconnect the radio battery:
WI2176B 1/17
StarLink
™
SLECDMA-CFB-PS &
SLE3/4G-CFB-PS
NFPA 2013 AHJ Inspection Guide
LED Verify this Condition Passed?
Yellow Operational LED D4 Blinks every 10 seconds (indicates normal operation).
Green RF Signal LED D3 Blinks at least 4 times (indicates minimally acceptable signal strength).
Red Trouble LED D5 OFF (indicates no trouble present).
LED
on the SLEULPS-R
Verify this Condition Passed?
Yellow Trouble LED Blinks once.
Trouble Relay Output Activates after 2 hours; check for proper trouble annunciation at FACP.
LED
on the SLEULPS-R
Verify this Condition Passed?
Yellow Trouble LED Blinks twice.
Trouble Relay Output
Activates within 200 seconds; check for proper trouble annunciation at
FACP
Yellow Trouble LED on the
SLEULPS-R
OFF (indicates no trouble present).
Yellow Trouble LED Turns off.
Trouble Relay Output Restores; check for proper trouble restoral at FACP.
Yellow Trouble LED Turns off.
Trouble Relay Output Restores; check for proper trouble restoral at FACP.
(continued)