The NAPCO SLE-CDMA-FIRE and SLECDMA-CFB Commercial Fire radios, fully compliant with the 2010 edition of
NFPA 72, are approved as fire alarm communicators. The capability of indicating and communicating signal failures to the
central station within 5 minutes of an outage allows the SLE-CDMA-FIRE or SLECDMA-CFB to replace existing tele-
phone lines.
The following testing guide is intended to assist with the AHJ inspection of a SLE-CDMA-FIRE or SLECDMA-CFB Fire ra-
dio installation. All required testing procedures are described, followed by the correct system responses. Ensure that in
cases where a radio trouble output is connected to an input on the FACP, the fire control panel properly annunciates the
trouble condition.
Normal LED Indications
With the SLE radio in standby mode, ensure the LEDs display as follows:
AC Failure Test
No Battery / Low Battery Test
The SLE-CDMA-FIRE and SLECDMA-CFB models are powered directly from the FACP power supply; radio AC
Failure and Battery Failure tests are not required.
Signal Loss Test
This test ensures that the SLECDMA-CFB-PS will indicate a supervisory trouble condition to the FACP and cen-
tral station upon loss of signal within the required time period.
Remove the antenna and observe the following indications:
(continued)
WI2177B 1/17
StarLink
™
SLE-CDMA-FIRE - SLECDMA-CFB
& SLE-GSM-FIRE - SLE3/4G-CFB
NFPA 2010 AHJ Inspection Guide
LED Verify this Condition Passed?
Yellow Operational LED D4 Blinks every 10 seconds (indicates normal operation).
Green RF Signal LED D3 Blinks at least 4 times (indicates minimally acceptable signal strength).
Red Trouble LED D5 OFF (indicates no trouble present).
LED Verify this Condition Passed?
Red Trouble LED D5 Blinks 5 times.
Yellow Trouble LED on
SLE-ULPS-R
Blinks 4 times.
Trouble Relay Output on
SLE-ULPS-R
Activates within 5 minutes; check for proper trouble annunciation at
FACP
Supervisory signal E356 will be received by the central station within
5 minutes of the antenna being removed.
Yellow Trouble LED on the
SLEULPS-R
OFF (indicates no trouble present).