36 NAPCO StarLink Fire: Getting Started Guide
Reconnect the antenna:
Note: In cases where the radio may be located in close proximity to the cell tower, there is a possibility that the
radio may operate properly, even with the antenna removed.
IP Signal Loss Test
This test ensures that the SLE-CDMAI-FIRE / SLE-GSMI-FIRE or SLECDMAI-CFB / SLE3/4GI-CFB will indicate a
supervisory trouble condition to the FACP and central station upon loss of signal within the required time period.
Remove the Ethernet cable and observe the following indications:
Reconnect the Ethernet cable:
(continued)
Red Trouble LED D5 Turns off.
Trouble Relay Output on
PGM1 Trouble Output
Restores; check for proper trouble restoral at FACP.
Supervisory restore signal R788 (zone 1) will be received by the cen-
tral station within 6 hours of the antenna being reconnected.
LED Verify this Condition Passed?
Red Trouble LED DS16 Blinks 1 time every 4 seconds.
Yellow Trouble LED DS15 Remains on solid.
Trouble Relay Output on
PGM1
Activates within 6 hours; check for proper trouble annunciation at
FACP
Supervisory signal E788 (zone 2) will be received by the central station
within 6 hours of the Ethernet cable being removed.
Green IP Network LED DS14 Turns off.
Red Trouble LED DS16 Turns off.
Yellow Trouble LED DS15 Slow blink.
Trouble Relay Output on
PGM1
Restores; check for proper trouble restoral at FACP.
Supervisory restore signal R788 (zone 2) will be received by the cen-
tral station within 6 hours of the Ethernet cable being reconnected.
Green IP Network LED DS14 1 Blink (Static IP) or 2 Blinks (DHCP)