Page 2 of 10 — DN-5262 • 10/31/05
Distributed voice options (XP transponders).
Firefighter telephone option.
30- to 120-watt high-efficiency amplifier.
Backup tone generator and amplifier option.
Dual channel option.
Telephone control module type ID.
Optional UDACT, 396-channel digital alarm communi-
cator transmitter with AC fail delay.
80-character displays (up to 32) for remote annunciation.
ACS annunciators (EIA-485), including LDM custom.
Two-wire detector interface provides compatibility with
many manufacturers' detectors for retrofit applications.
Integral printer interface (80-column and 40-column
printers).
Integral 80-character LCD display, backlit (2 lines x 40
characters).
Field-programmable on panel or on PC, with program
check, compare, simulate.
Full QWERTY keypad behind flip-down door.
Autoprogramming and Walk Test.
Identifies two devices set to the same address.
History file with 800-event capacity in nonvolatile
memory, plus separate 200-event alarm-only file.
Programmable waterflow or supervisory selection per
point.
Alarm Verification selection per point, with tally.
Verification Trouble counter. Trouble indication after a
detector verifies 20 times.
Programmable Positive Alarm Sequence (PAS) Presignal
per NFPA 72.
Silence inhibit and Auto Silence timer options.
Programmable non-alarm points for lower priority func-
tions.
Remote ACK / Silence / Reset / Drill via addressable
modules.
Maintenance Reports may be sorted via PC by compen-
sation value (dirty detector), peak alarm value, or address.
Automatic time control functions, with holiday exceptions.
Dual rate charger for up to 90 hours of standby power.
Rapid poll algorithm for manual stations. Responds to
alarm/activation in less than three seconds.
SLC loop maximum length 10,000 feet (3,048 m) @ 12
AWG (3.31 mm²).
Surface Mount Technology (SMT) electronics.
High-speed RISC 16-bit microprocessor.
Extensive built-in transient protection.

Other manuals for Notifier AFP-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-400 and is the answer not in the manual?

Notifier AFP-400 Specifications

General IconGeneral
BrandNotifier
ModelAFP-400
CategoryControl Panel
LanguageEnglish

Related product manuals