88
88
8 Voice Alarm Multiplex 15889:F2 10/01/01
20
AMG-1 and the ACM-16AT
Set the address of the AMG-1 Audio Message Generator via DIP switches 2 and 3. This address can only be
set for 29-32 for a standard AMG-1 or 25-28 for an AMG-1 with an AMG-X4 EPROM installed. The highest
possible address setting is recommended. This allows the AMG-1 functions to assume the first four points on
an ACM-16AT set to address "1." Up to eight AMG-1s may be installed in an AM2020/AFP1010 system.
For AMG-1s set in the address range 25-28 (AMG-X4 EPROM required):
ACM-16AT Address A01
For AMG-1s set in the address range A29-A32:
AEM-16AT
(the first expander of the ACM-16AT at address 1 (see above)
Annunciator points P01-P04
Control tone/messages
selection for AMG-1
Address 32
Annunciator points P05-P08
Control tone/messages
selection for AMG-1
Address 31
Annunciator points P09-P12
Control tone/messages
selection for AMG-1
Address 30
Annunciator points P13-P16
Control tone/messages
selection for AMG-1
Address 29
Annunciator points P17-P20
Control tone/messages
selection for AMG-1
Address 28
Annunciator points P21-P24
Control tone/messages
selection for AMG-1
Address 27
Annunciator points P25-P28
Control tone/messages
selection for AMG-1
Address 26
Annunciator points P29-P32
Control tone/messages
selection for AMG-1
Address 25
Boston Code (
Note:
requires VROM-109 to be installed in VROM-B position)
The special Boston Code, which appears on the following two pages, will function as follows:
1) Pause.
2) All Call is initiated.
3) One round of Code Four (four pulses of a 900 Hz tone followed by a 1 second pause).
4) VROM B (VROM-109) is played three times.
5) All Call is deactivated.
5) Fifteen second pause.
6) Continuous Temporal.