66
References
A. Specications
*1 For BN150R, the maximum output (1.5kVA/1.35kW) cannot be used with the standard input plug (NEMA 5-15P). To use with maxi-
mum output, replace with a 20A plug. (A 20A plug is included in the accessories.)
*2
For BN300R, the maximum output (3.0kV
A/2.7kW) cannot be used with the standard input plug (NEMA L5-30P). To use with maxi-
mum output, connect to the terminal block (purchased separately).
The standard equipment input plug (NEMA L5-30P) cannot be connected to a household receptacle.
*3
Rectiedload,ratedload,inBatteryMode(exceptinBL
state)
*4
Rated load/ Rated input voltage/ When fully charged
*5
Rated load/ Rated input voltage/ When battery charge current is at maximum
Model BN75R BN150R BN300R
Method Operation method Line-interactive method
Cooling method Forced air cooling
Input Rated input voltage 100 VAC
Input
voltage
range
Sensitivity setting: Standard
89±3 to 118V±3 VAC
Sensitivity setting: Low
84±3 to 118V±3 VAC
Sensitivity setting: High
89±3 to 113V±3 VAC
Input maximum current 12A 20A 40A
Frequency 50/60Hz±4Hz
Phase Single-phase, two-wire (grounded)
Input protection NFB(13A) NFB(25A) NFB(45A)
AC input plug 3P (NEMA 5-15P) 3P (NEMA 5-15P) *1 3P (NEMA L5-30P) *2
Output Rated output capacity 750VA/680W 1500VA/1350W *1 3000VA/2700W *2
Voltage Commercial operation 90±3 to 114V±3 VAC (Sensitivity setting: Standard)
84±3 to 114V±3 VAC (Sensitivity setting: Low)
90±3 to 110V±3 VAC (Sensitivity setting: High)
Backup operation 100 VAC±6%
Frequency Commercial operation Synchronized with input frequency
Backup operation 50/60Hz±0.1Hz
Waveform Commercial operation Sine wave
Backup operation Sine wave
Distortion rate *3 20%max.(Rectiedload,atratedoutput)
15% max. (Resistance load, at rated output)
Phase Single-phase, two-wire (grounded)
Output receptacles NEMA 5-15R x 4 NEMA 5-15R x 6 NEMA 5-15R x 6
NEMA 5-20R x 2
Battery Type Sealed lead battery
Voltage / Capacity x Quantity 6 V / 9 Ah × 4 12 V / 9 Ah × 4 12 V / 9 Ah × 6
Backup time
(25°C, initial characteristics)
4 min. or more 4.5 min. or more 2.5 min. or more
Charging time *7 4 hours 90%
Battery life Ambient temperature
25°C
Expected life: 5 years
Environment
Operating environment temperature/
humidity
0°C to 40°C, 25 to 85%RH with no condensation
Storage temperature -15°C to 50°C, 10 to 90%RH with no condensation
Safety standard / RoHS directive
compliance
UL1778 / RoHS compliant / CE
Disturbance voltage / Radiated
interferenceeldstrength
VCCI Class A
Internal power consumption (normal/
maximum)
50W (*4) / 100W (*5) 100W (*4) / 200W (*5) 150W (*4) / 300W (*5)
Noise 38 dB max. 50 dB max. 50 dB max.
Dimensions (W x D x H) 438mm x 512mm x 43mm 438mm x 437mm x 87mm 438mm x 650mm x 87mm
Weight of unit Approx. 13.5kg Approx. 21.5kg Approx. 32kg