172
Specifications Section 5-1
5-1-2 Output Function Block Diagram
5-1-3 Output Specifications
If the set value is outside the specified range provided below, an output setting
error will occur, and the output specified by the output hold function will be
output.
Range: 1 to 5 V (4 to 20 mA)
Analog Output Unit CPU Unit
D/A
Analog output 1
Same as above.
Analog output 2
Same as above.
Analog output 3
Same as above.
Analog output 4
Output hold
enabled
Output hold
disabled
Output value,
hold
Output value,
no hold
Special I/O
Unit Area
Analog
output 1
set value
Only analog outputs 1 and 2
are used by the CJ1W-DA021.
5.2 V (20.8 mA)
5 V (20 mA)
1 V (4 mA)
0.8 V (3.2 mA)
0000
(0000)
FF38
(FE70)
0FA0
(1F40)
1068
(20D0)
Resolution: 4,000/8,000
Set value (16-bit binary data)
Analog output signal
( ): Values in parentheses are for a
resolution of 8,000.