6 - 43
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-7 Initial Setting Level
6
in-t
Input Type
• The Input Type parameter is used to set the input type.
• When this parameter is changed, the set point limiter is changed to the defaults. If the
limiter must be specified, set the SP Upper Limit and SP Lower Limit parameters (Initial
Setting Level) again.
• If a resistance thermometer is mistakenly connected while a setting for other than a
resistance thermometer is in effect, s.err will be displayed. To clear the s.err display,
check the wiring and then cycle the power.
Related Parameters
Temperature Unit (Initial Setting Level): Page 6-44
Set Point Upper Limit and Set Point Lower Limit (initial Setting Level): Page 6-45
* This range can be used only for E5CC-U Digital Controllers and only if they are manufactured i
May 2014 or later (version 2.2 or higher).
Input type
Sensor
specification
Set value
Temperature
range in °C
Temperature
range in °F
Resistance
thermometer
Pt100
0 −200 to 850 −300 to 1500
1 −199.9 to 500.0 −199.9 to 900.0
2 0.0 to 100.0 0.0 to 210.0
JPt100
3 −199.9 to 500.0 −199.9 to 900.0
4 0.0 to 100.0 0.0 to 210.0
Thermocouple
K
5 (default) −200 to 1300 −300 to 2300
6 −20.0 to 500.0 0.0 to 900.0
J
7 −100 to 850 −100 to 1500
8 −20.0 to 400.0 0.0 to 750.0
T
9 −200 to 400 −300 to 700
10 −199.9 to 400.0 −199.9 to 700.0
E11−200 to 600 −300 to 1100
L12−100 to 850 −100 to 1500
U
13 −200 to 400 −300 to 700
14 −199.9 to 400.0 −199.9 to 700.0
N15−200 to 1300 −300 to 2300
R 16 0 to 1700 0 to 3000
S 17 0 to 1700 0 to 3000
B 18 0 to 1800 0 to 3200
C/W 19 0 to 2300 0 to 3200
PLII 20 0 to 1300 0 to 2300
Infrared
Temperature Sensor
ES1B
10 to 70°C 21 0 to 90 0 to 190
60 to 120°C 22 0 to 120 0 to 240
115 to 165°C 23 0 to 165 0 to 320
140 to 260°C 24 0 to 260 0 to 500
Current input
4 to 20 mA 25 One of the following ranges according to
the scaling:
−1999 to 9999
−199.9 to 999.9
−19.99 to 99.99
−1.999 to 9.999
0 to 20 mA 26
Voltage input
1 to 5 V 27
0 to 5 V 28
0 to 10V 29
0 to 50 mV* 30