6 - 87
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Advanced Function Setting Level
6
sptr
SP Tracking
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
The Remote SP Enable parameter must be set to
ON (default: OFF).
• This parameter sets the operation to perform when moving from Remote SP Mode to
Local SP Mode.
• When this parameter is set to ON, operation continues using the remote SP as the local
SP.
• When this parameter is set to OFF, the remote SP does not affect the local SP.
Related Parameters
Set Point During SP Ramp (Operation Level): Page 6-10
SP Mode (Adjustment Level): Page 6-21
ST (self-tuning) (Initial Setting Level): Page 6-46
Remote SP Enable (Advanced Function Setting Level): Page 6-85
p-db
PV Dead Band A Position-proportional Model must be used.
When the PV enters the PV dead band, any unnecessary output is stopped to prevent the
valve from deteriorating.
Related Parameters
Close/Floating, Motor Calibration, and Travel Time (Initial Setting Level): Page 6-59
Position Proportional Dead Band (Adjustment Level): Page 6-35, Open/Close Hysteresis
(Adjustment Level): Page 6-36
Setting range Default
on: Enabled or off: Disabled off
SP
PV
Unnecessary output is
stopped in this range.
PV Dead Band
Setting range Unit Default
0 to 9999 EU 0