E5CS-X E5CS-X
41
J FUNCTION SELECTOR SWITCH
The function selector switch is a 6-pin in-line DIP switch. The
following table shows the selection made by each switch position.
ON
165432
PX
ON
Function Switch number P X 1 2 3 4 5 6
Key protection for
Enables protection ON
Up/Down keys
Disables protection OFF
Used for factory-authorized Not used in normal
ON
calibration only operation
OFF
Control mode
PID action ON
ON/OFF action OFF
Proportional period
2 seconds ON
20 seconds OFF
Control output
Normal ON
Reverse OFF
Input shift function
Enabled ON
Disabled OFF
RTD sensor input standard
DIN ON
JIS OFF
Scale indication for dual-
°F ON
scale range selection
°C OFF
J CONTROL MODE SELECTION
ON/OFF Action
Switch 1 of the function selector DIP switch is factory-set to OFF,
so the temperature controller performs ON/OFF control
action.Set switch 3 to ON when the temperature controller is
used to control a cooling device such as a chiller or freezer.
Control output ON
OFF
Set temperature
Switch 1 OFF:
Temperature controller performs ON/OFF action.
ON
165432
PX
ON
Control output ON
OFF
Set temperature
Switch 3 ON:
Used for cooling operations in ON/OFF action.
ON
165432
PX
ON
PID Action
Set switch 1 of the function selector DIP switch to ON to perform
PID control action. Follow the steps described below
Determining Proportional Period
Set switch 2 of the function selector DIP switch to OFF to select a
proportional period of 20 seconds. This is used when the PID
control action is performed with the contact output of the
temperature controller, or when using an external relay or
contactor.
Control ON
output
OFF
20 seconds
Switch 2 OFF:
Proportional period is 20 seconds.
ON
165432
PX
ON
When a quick response in required, set switch 2 to ON to select a
proportional period of 2 seconds. Even when a solid state relay
(SSR) is used, set the 2-second proportional period only when
quick response is essential. Avoid using this setting with a
contact output because it will shorten the relay’s service life.
Control ON
output
OFF
2 seconds
Switch 2 ON:
Proportional period is 2 seconds.
ON
165432
PX