Section 4 Operations for Applications
4-8
Operations for
Applications
4.5 Alarm
Delays
Alarm Delays
Delays can be set for the alarm outputs. ON and OFF delays can be
set separately for alarms 1 and 2. The ON and OFF delays for
alarms 1 and 2 also apply to the individual ALM1 and ALM2
indicators. The alarm ON delays will also function when the power is
turned ON.
Operation of Alarm ON and OFF Delays (for an Upper-limit Alarm)
The alarm will not turn ON if the time that the alarm is ON is equal to
or less than the ON delay set time. Also, the alarm will not turn OFF
if the time that the alarm is OFF is equal to or less than the OFF
delay set time.
If an alarm turns OFF and then back ON during the ON delay time,
the time will be remeasured from the last time the alarm turns ON.
Also, if an alarm turns ON and then back OFF during the OFF delay
time, the time will be remeasured from the last time the alarm turns
OFF.
Alarm status
PV
Alarm
setting
ON delay
set time
OFF delay
set time
Alarm latch = OFF
Alarm will not turn
ON.
Alarm hysteresis
ON delay
set time

Table of Contents

Other manuals for Omron E5CSV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CSV and is the answer not in the manual?

Omron E5CSV Specifications

General IconGeneral
BrandOmron
ModelE5CSV
CategoryTemperature Controller
LanguageEnglish

Related product manuals