H5CR H5CR
2
Description Part number
Panel mounting bracket (one supplied with H5CR-B and H5CR-S models) Y92F-30
REPLACEMENT PARTS
Part number H5CR-L H5CR-B H5CR-S
Classification Economy type Standard type Short body type
AC 100 to 240 VAC, 50/60 Hz, 100 to 240 VAC, 50/60 Hz,
24 VAC, 50/60 Hz 24 VAC, 50/60 Hz
DC 12 to 24 VDC, 20% max. 12 to 24 VDC, 20% max.
permissible ripple permissible ripple
Operating voltage 85% to 110% of rated voltage
AC 3 VA at 60 Hz, 240 VAC
DC 1 W at 24 VDC 2 W at 24 VDC
Inputs Types available Reset and start signal Reset, gate, start signal, and key protect
Signal, Type No-voltage input
reset ON impedance 1 k max. (Approx. 2 mA when 0)
and gate Residual voltage 2 V max. in ON state
OFF impedance 100 k minimum
Pulse width 1 ms or 20 ms selectable for reset and signal
20 ms for gate
Key Type No-voltage input
protect ON impedance 100 k max. (Approx. 2 mA when 0)
Residual voltage 1 V max. in ON state
OFF impedance 100 k minimum
Response time 1 second
Type Time limit SPDT relay output or NPN open collector transistor output (H5CR-S)
Instantaneous
Relay Max. load 5 A, 250 VAC resistive load (p.f. = 1)
Min. load 10 mA, 5 VDC
Solid- Max. load 100 mA, 30 VDC
state Residual voltage 2 V max., 1 V typical
Repeat accuracy Power start ±0.01%, ±0.05 second max.
Signal start ±0.005%, ±0.03 second max. (rate for set value)
Setting error
Resetting system Power reset (A, A-1, A-2, B, D and E modes)
External, manual, automatic resets (may be internal depending on A-1, B, B-1, D and E
operation modes)
Resetting time Power reset 0.5 second minimum (A, A-1, A-2, B, D and E modes)
Indicators 4-digit LCD alphanumeric 4-digit LCD alphanumeric display with backlighting
display without backlighting 8 mm (0.32 in) H present value, 4 mm (0.16 in) H set value
8 mm (0.32 in) H present
value, 4 mm (0.16 in) H
set value
Specifications
Supply
voltage
Power
consumption
Control
output
*One-shot time, seven choices selectable:
0.1 sec, 0.5 sec, 1 sec, 5 sec, 10 sec, 15 sec, 20 sec
Range selection Time unit Maximum setting
- . - - - s 0.001 second 9.999 seconds
- - . - - s 0.01 second 99.99 seconds
- - - . - s 0.1 second 999.9 seconds
- - - - s 1 second 9999 seconds
- - min - - s 1 second 99 minutes 59 seconds
- - - . - min 0.1 minute 999.9 minutes
- - - - min 1 minute 9999 minutes
- - hr - - min 1 minute 99 hours 59 minutes
- - - . - hr 0.1 hour 999.9 hours
- - - - hr 1 hour 9999 hours
RANGE AND OPERATION MODE SELECTION
Mode Operation Output type
A ON-delay Sustained or
A-1 Sustained start signal ON-delay one-shot*
A-2 Power ON-delay
A-3 Power ON-delay/non-power
resettable
B Repeat cycle
B-1 Repeat cycle/non-power
resettable
D OFF-delay Sustained
E One-shot
F Cumulative signal ON-delay