Digital Daily Time Switch H5F 3
Connections
■ Terminal Arrangement
Note: 1. The Time Switch uses M3.5 terminals.
2. The Time Switch output is no-voltage contact output. An external power supply is required to drive the load.
3. Applicable wire: 600-V vinyl-insulated wire (solid wire or twisted wire, copper), 14 to 24 AWG, 2 wires max. per terminal.
4. Applicable tightening torque: 0.98 to 1.17 N·m.
5. Recommended fuse: T2A, 250 VAC, time delay, low breaking capacity.
Operation
■ Operation
Note: Up to 12 ON/OFF operations are possible per day. (For pulse-output operation, the number is 24.)
H5F-B H5F-FB
H5F-KB
PW
ON
PM
PM
3
00
5
00
H5FTIME SWITCH
SU MO TU WE TH FR SA
PW
ON
PM
PM
3
00
5
00
H5FTIME SWITCH
SU MO TU WE TH FR SA
Flush Mounting Models
Power source
100 to 240 VAC
Power source
100 to 240 VAC
Power supply
of load
Load
Power supply
of load
Load
Power source
100 to 240 VAC
Power supply
of load
Load
Surface Mounting Models
Surface Mounting/Track Mounting Models
(Rear View)
(Front View)
(Front View)
WRITE
m
/ WD
d
h
SELECT
MODE
CLR
OUT
POWER
ON
AUTO
OUT
OFF
TESTHOLIDAY+1h
TMR/
P
P
WRITE
m
/ WD
d
h
SELECT
MODE
CLR
OUT
POWER
ON
AUTO
OUT
OFF
TESTHOLIDAY+1h
TMR/
P
P
Operation method Digital quartz
Time range 24 h
´ 7 days (Operation days can be specified.)
Operation 1. Daily operation (Multiple-day operation possible.)
2. Pulse-output operation (Pulse width can be set in units of 1 s from 1 to 59 s and in units of 1 min
from 1 to 60 min.)
3. Partial operation on specified day (One or some of the operations for certain days can also be
executed on other days.)
4. Forced ON/OFF operation
5. Holiday operation
6. Output override and automatic return operation
Display 1. Day, hours (12-hour (am/pm) or 24-hour clock), minutes (0:00 to 11:59 a.m./ 0:00 to 11:59 p.m.,
0:00 to 23:59)
2. Digital display by LCD. Character height: 8 mm
3. Digital display of present time and time schedules for operation
4. Timing chart display of present time and time schedules for operation
Other functions Program check function, summer time function
Number of circuits 1 independent circuit
Minimum setting unit 1 min
Minimum set interval 1 min
Number of operations that can be set 24 (see note)