S8VS
Specifications
Ratings/Characteristics
Power ratings 15 W 30 W
Item Type Standard Standard
Efficiency (typical)
(rated input voltage)
5-V models 72% min. 70% min.
12-V models 74% min. 76% min.
24-V models 77% min. 80% min.
Input
Voltage *1 100 to 240 VAC (allowable range: 85 to 264 VAC)
Frequency *1 50/60 Hz (47 to 450 Hz)
Current
With 100-VAC input 0.45 A max. 0.9 A max.
With 200-VAC input 0.25 A max. 0.6 A max.
Power factor ---
Harmonic current regulation Conforms to EN61000-3-2
Leakage current
With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2
With 100-VAC input 25 A max.
With 200-VAC input 50 A max.
Output
Voltage adjustment range *3 10% to 15% (with V.ADJ)
Ripple 2.0% (p-p) max. (at rated input/output voltage)
Input variation influence 0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage)
2.0% max. (5 V), 1.5% max. (12 V, 24 V), (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Startup time *2 100 ms max. (at rated input/output voltage) 1,000 ms max. (at rated input/output voltage)
Hold time *2 20 ms min. (at rated input/output voltage)
Additional
functions
Overload protection *2
105% to 160% of rated load current, inward-sloping voltage
drop, automatic reset
105% to 160% of rated load current, inverted L voltage drop,
intermittent operation, automatic reset
Overvoltage protection *2 Yes (a zener diode clamp) *4 Yes *5
Output voltage indication No
Output current indication No
Peak-hold current indication No
Maintenance forecast monitor indication No
Maintenance forecast monitor output No
Total run time monitor indication No
Total run time monitor output No
Undervoltage alarm indication Yes (color: red)
Undervoltage alarm output No
Parallel operation No
Series operation
Models with 24-V output: Possible for up to 2 Power Supplies (with external diode)
Models with 5- or 12-V output: Not possible
Other
Operating ambient temperature Refer to the derating curve in Engineering Data (15-W, 30-W Models). (with no icing or condensation)
Storage temperature 25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI
Conducted
Emissions
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Radiated Emissions Conforms to EN61204-3 EN55011 Class B
EMS Conforms to EN61204-3 high severity levels
Approved standards
UL: UL508 (Listing; Class 2 Output: Per 1310), UL1604 (Class I/Division2), UL60950-1
cUL: CSA C22.2 No.14 (Class 2 Output), No.60950-1, No.213 (Class I/Division2)
cUR: CSA C22.2 No. No.60950-1
EN/VDE: EN50178 (=VDE0160)
SEMI F47-0706 (With 200-VAC input)
Weight 160 g max. 180 g max.
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data (15-W, 30-W Models) on page 14 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4.
The overvoltage protection of the S8VS-015
@@
uses a zener diode clamp. If the internal feedback circuit is destroyed by any chance, the load
may be destroyed by the clamped output voltage (approx. 140% to 190% of the rated output voltage).
*5. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.